8.2.8 Over voltage or too low voltage protection diagnosis and solution (P1)
Error Code
Malfunction decision
conditions
Supposed causes
Trouble shooting:
Check the power supply
Yes
Check the connections and
wires
Yes
Power on and when the unit is in standby,
check if the voltage between P and N is
around DC 310V or 340V or 380V? Then
start up the unit, measure the voltage
between P and N. Is it in 220V~400V?
Yes
Check the reactor
Yes
Replace the reactor
P1
An abnormal voltage rise or drop is detected by checking the
specified voltage detection circuit.
Power supply problems.
System leakage or block
PCB faulty
No
No
No
No
Stop the unit
Correct the connections or
replace the wires.
Replace the IPM board
Replace outdoor main PCB