Combustion And Input Check - American Standard S9V2B080D4VSAB Installer's Manual

Upflow/horizontal and dedicated downflow gas-fired, direct/non-direct vent, 2–stage condensing variable speed furnaces with variable speed draft inducer
Table of Contents

Advertisement

Combustion and Input Check

1.
Make sure all gas appliances are off except the furnace.
2.
Clock the gas meter with the furnace operating (determine the
dial rating of the meter) for one revolution.
3.
Match the "Sec" column in the gas flow table with the time
clocked.
4.
Read the "Flow" column opposite the number of seconds clocked.
5.
Use the following factors if necessary:
a.
For 1 Cu. Ft. Dial Gas Flow CFH = Chart Flow Reading ÷ 2
b.
For 1/2 Cu Ft. Dial Gas Flow CFH = Chart Flow Reading ÷ 4
c.
For 5 Cu. Ft. Dial Gas Flow CFH = 10X Chart Flow Reading ÷ 4
6.
Multiply the final figure by the heating value of the gas obtained
from the utility company and compare to the nameplate rating.
This must not exceed the nameplate rating.
18-CE03D1-1F-EN
F F u u r r n n a a c c e e G G e e n n e e r r a a l l I I n n s s t t a a l l l l a a t t i i o o n n
Gas Flow in Cubic Feet Per Hour
2 Cubic Foot Dial
Sec.
Flow
Sec.
Flow
10
732
31
236
11
666
32
229
12
610
33
222
13
563
34
215
14
523
35
209
15
488
36
203
16
458
37
198
17
431
38
193
18
407
39
188
19
385
40
183
20
366
41
179
21
349
42
174
22
333
43
170
23
318
44
166
24
305
45
163
25
293
46
159
26
282
47
156
27
271
48
153
28
262
49
149
29
253
50
146
30
244
51
144
Sec.
Flow
Sec.
Flow
52
141
86
85
53
138
88
83
54
136
90
81
55
133
94
78
56
131
98
75
57
128
100
73
58
126
104
70
59
124
108
68
60
122
112
65
62
118
116
63
64
114
120
61
66
111
130
56
68
108
140
52
70
105
150
49
72
102
160
46
74
99
170
43
76
96
180
41
78
94
190
39
80
92
200
37
82
89
84
87
21