Semi-Flush Mount Backbox - Honeywell Fire-Lite Alarms LCD-80F Manual

Remote fire annunciator
Table of Contents

Advertisement

Mounting
3.2

Semi-flush Mount Backbox

Mounting in SBB-3 Three Gang Electrical Box
Remove the plug-in terminal blocks from the LCD-80F circuit board.
Connect the EIA-485 and power wiring into the terminal block positions
illustrated in Figure 1-2 on page 9, Figure 4-1 on page 24 and Figure 4-
2 on page 25. Plug the terminal blocks back into the P2 and P1 connec-
tors on the back of the annunciator. Set DIP switch SW1 for the desired
options. Refer to Figure 1-4 on page 13.
Carefully insert the LCD-80F into the three-gang electrical box P/N:
10103 or three electrical boxes ganged together and attach it using the
four mounting holes on the LCD-80F flange and the four screws
provided for this purpose. Replace the trim ring and secure with the two
screws which were previously loosened. Adjust the plastic trim ring to
the surface of the wall before tightening the screws. Do not overtighten.
Figure 3-3:
Mounting in SBB-3 Box
The LCD-80F can be semi-flush mounted in a three-
gang electrical box, P/N 10103 or equivalent, with a
minimum depth of 2 3/16". The LCD-80F can also
be mounted in three gangable electrical switch
boxes connected together as illustrated in Figure 3-4
on page 22.
Important! When installing conduit in a 3-gang
electrical box, use knockouts on the top or bottom.
Installing conduit on the sides or back of some boxes
may interfere with mounting of the LCD-80F in the
box.
flange
LCD-80F
Document 51338 Rev. B 08/24/05 P/N 51338:B
mounting holes (4)
Three-gang electrical box P/N 10103
Semi-flush Mount Backbox
LCD-80F flange
FIRE ALARM ANNUNCIATOR
AC Power
Alarm
Trouble
Supervisory
Drill
Ack/Step
Silence
Reset
Hold 2 sec.
3-gang electrical box P/N 10103
EIA-485 and power wiring
Alm. Silenced
21