3.15 ATS Configuration Menu

Note: The ATS Configuration menu appears only if a
Model RXT transfer switch is connected.
Use the ATS Configuration submenu to check the Model
RXT transfer switch system settings and time delays,
and change the settings, if necessary.
Changing ATS Configuration Settings
To enable editing, press the select button. The value
flashes to indicate that it can be changed. Press the up
and down arrow buttons to change the value. Press the
Select button to save the value shown.
Use the up and down arrow buttons to move to the next
value to be changed. Repeat the adjustment process
until all values are correct.
Press the down arrow until Return is displayed. Press
the select button to return to the main menu.
40
Section 3 RDC2 Controller Operation
ATS ---->
Configuration
Figure 3-15 ATS Configuration Menu
Normal Freq:
60.0 Hz
Normal Voltage:
240.0 V
Emerg. Freq:
60.0 Hz
Emerg. Voltage:
240.0 V
Emerg. Engine
Start: 3 sec
Transfer From
Normal: 3 sec
Transfer From
Emerg.: 120 sec
<---- Return