Warning (W) or
Shutdown (SD) Condition
Fault
AC Sens Lost
W (1 sec.)
SD (3 sec.)
Accy PwrOver
W
Warning
Alt Protect
SD
Shtdwn
ATS Com Error
W
ATS PhaseRot
W
Aux Input
SD
Batt Chg Flt
W
Battery Voltage
W
High
Battery Voltage
W
Low
CAN comm
SD
fault
Engine Coolant
SD
Temperature
High
Engine Oil
SD
Pressure Low
EngineSpeed
SD
High
EngineSpeed
SD
Low
24
Section 2 Generator Set Operation
AC Sensing Lost. In Auto mode, generator
output AC sensing is lost. Starts 10 seconds
after crank disconnect.
Warning: after 1 second if no output detected
after crank disconnect.
Shutdown: after 3 seconds if voltage was
present and then lost.
Accessory Power Overload. An over current
fault (short circuit) on the accessory controller
power output.
High generator current has been detected. The
generator set shuts down to protect the
alternator from damage caused by overheating
the windings. (38RCL only)
Ats Communication Error. Warning is displayed
if RXT interface connection is lost. See
Section 2.6.3.
ATS Phase Rotation Mismatch. Transfer switch
phase rotation does not match. ATS will not
transfer.
Auxiliary Input. An optional customer-connected
input is closed. (Digital input from optional PIM.)
Battery charger fault. Input to PIM from an
external battery charger (not the built-in battery
charger).
Engine starting battery voltage rises above
125% of the battery voltage setting for more than
10 seconds. Inhibited during the engine crank
cycle.
Clears when the battery voltage returns to an
acceptable level.
Engine starting battery voltage falls below the
battery voltage setting (typically 12.5 volts) for
more than 90 seconds when the engine is not
running. Inhibited during the engine crank cycle.
Clears when the battery voltage returns to an
acceptable level.
Engine CAN communications fault.
Engine coolant temperature exceeds the
maximum temperature for more than 5 seconds.
Function becomes active after crank disconnect.
The engine ECM indicates low oil pressure for
more than 5 seconds. Function becomes active
30 seconds after crank disconnect (30 second
inhibit).
Note: The low oil pressure shutdown does not
protect against low oil level. Check the engine
oil level regularly as recommended in Section 4.
Engine speed exceeds 115% of the normal
running speed for more than 0.3 seconds.
Engine speed drops below 85% of the normal
running speed for more than 3 seconds.
Check
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Reduce the load.
Check communication wiring between
transfer switch interface board and
generator set.
Correct the ATS connection. Refer to
the ATS Installation manual, wiring
diagrams, and labels on the transfer
switch.
Check customer-supplied equipment.
Check external battery charger.
Check the battery rating and
condition.
Check the battery charger operation.
Check the battery rating and
condition.
Check the battery charger operation.
Charge or replace the battery.
Check wiring to ECM.
Check power to ECM.
Check for blocked air inlets and
exhaust outlets.
Check for leaks in the lubrication
system.
Check the oil level and add oil if the
level is low.
Contact an authorized
distributor/dealer for service.
Reduce the load.
Contact an authorized
distributor/dealer for service.
TP-6810 7/16