Vent Damper Harness - Molex Plug - UTICA BOILERS UH15B Series Installation, Operation & Maintenance Manual

Cast iron gas fired boiler
Table of Contents

Advertisement

B.1 Vent Damper Harness - Molex Plugs
!
WARNING
Do Not negate the action of any existing safety
orperational controls. Avoidance of these in-
structions could result in death or serious injury.
When servicing controls, all wires must be
Note
labeled prior to disconnection. Wiring errors
can cause improper and dangerous operation.
Do not turn damper open manually or motor
damage will result and void all warranties, use
the service switch.
DO NOT CUT PLUG OFF OF DAMPER MOTOR
ASSEMBLY OR WARRANTY WILL BE VOID.
Check Molex Plugs on Vent Damper Harness:
Damper wiring harness is made up of 4
Note
individual colored wires, Brown, Black, Yellow,
and Orange (refer to drawing below).
1.
Disconnect thermostat wires.
2.
Use the two diagrams below to confirm the Molex plugs
on each end of the damper harness are wired and
operating properly.
Damper end of wiring harness:
A. Hold plug in hand with wiring harness behind Molex
with "V" slot on top. Verify wire colors are in
proper position.
B. Take reading across brown and black wires in Molex
plug, using test meter set for AC volts. 24 volts
should be present.
i.
IF NOT, source of the problem is not in
damper; check line voltage and 24 volt supply.
ii. If 24 volts is present across brown and black,
continue to step iii.
iii. Reconnect thermostat wires and turn up heat
setting.
iv. Check voltage across black and orange wires
in Molex plug. 24 volts AC should be present:
• IF NOT, source problem is not the damper.
• If 24 volts is present continue on to step v.
v. Place jumper wire across orange and yellow
wires in Molex plug (see Below). This will
create bypass of the damper, boiler should
then ignite.
• IF NOT, source problem is not the damper. Go to
"Aquastat end of wiring harness'
APPENDIX B - VENT DAMPER
Control End of wiring harness
Hold plug in hand with wiring harness behind Molex with
"V" slot on top. Verify wires colors are in proper position
32
• If boiler ignites: Go to section B.2 page
33. "Vent Damper Troubleshooting Guide".
NOTE: Prior to replacing the damper, verify
"V" Slot
Brown
Yellow
"V" Slot
Black
OPEN
problem is not with wire connections between
damper and wiring harness.
A. Remove damper harness from control. Jump Molex
connector on control board between two center
holes using ~18ga. thermostat wire.
i.
If boiler ignites, replace damper harness
ii. If boiler does not light, replace control.
Orange
Black
Yellow
Brown
Orange
Black