Check vent damper and all flue product carrying
areas of boiler annually for deterioration from
corrosion or other sources. If you see corrosion or
other deterioration, contact your service agent for
repairs.
Check vent damper operation as follows:
1.
When boiler is off, check vent damper positions
indicator points to closed position. See Figure 12.
2.
Turn thermostat or controller up to call for heat and
check vent damper indicator points to open position
See Figure 12.
3.
Turn thermostat or controller down again and check
damper position indicator returns to closed position.
4.
Return thermostat to desired position.
Inspect vent damper at least once a year by
trained service technician.
!
WARNING
Asphyxiation or burn hazard. Improper operation of
vent damper may result in serious injury or death
due to fire or to asphyxiation from poisonous gases
such as carbon monoxide which is odorless and
invisible.
Manual Operation of Vent Damper
• Place vent damper in open position to permit burner
operation by using "HOLD DAMPER OPEN" switch,
located on damper controller.
• Thermostat controls burner firing as before, while
damper remains open.
• DO NOT turn damper open manually, motor damage
will result.
• Set switch to "AUTOMATIC OPERATION" to close vent
damper during burner off cycle.
• For further information, and for vent damper
troubleshooting guide, refer to manual packaged with
vent damper.

VENT DAMPER OPERATION

Figure 10 - Horizontal Installation
To Boiler Vent Damper
Figure 11 - Alternate Vent Damper Installation
Caution: Do not
install Vent Damper
within 6" (152mm)
of combustible
Install Damper Here
Boiler
Figure 12 - Vent Damper Position Indicator
Flow
15
Horizontal Installation
Flow
Chimney
T
o
Chimney
Vent Damper
Flow
To Boiler
material
Damper Closed
Showing Open and Closed Positions
NO
YES
YES
T
NO
o
Install vent damper
with actuator to sides
of vent only. Do not
mount above or below
vent.
Actuator may
be installer in
any position.
Do Not
Install
Here
Chimney
Water Heater
Damper Open

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Peg150eidPeg187eidPeg225eidPeg112eidPeg262eidPeg299eid

Table of Contents