DAMPER INSTALLATION
NOTE: Refer to Figure 11 for steps 1-6.
Figure 12 - Damper Motor Wiring
Place Vent Damper on or as close to vent outlet of
1.
boiler as possible. Figure 13.
Remove Vent Damper Motor cover.
2.
Feed damper wire harness connector through bracket
3.
hole on Damper Motor frame.
Tighten locknut onto Damper wire harness connector.
4.
Plug Damper connector into socket on Damper Motor
5.
frame.
Replace Damper Motor cover and wire Damper in
6.
accordance with Figure 12.
Vent daMper InstallatIon & InstructIons
DAMPER INSTRUCTIONS
Figure 13 - Vent Damper Placement
Verify only boiler is serviced by Vent Damper.
1.
13.
Clearance of not less than 6 inches (152mm) between
2.
Vent Damper and combustible material must be
maintained. Additional clearance should be allowed for
service of Vent Damper.
Vent Damper must be in the open position when
3.
appliance main burners are operating.
The Vent Damper position indicator must be in a visible
4.
location following installation.
The thermostat's heat anticipator must be adjusted to
5.
match the total current draw of all controls associated
with the boiler during a heating cycle.