Toshiba RAS-3M26S3AV-E Service Manual page 36

Table of Contents

Advertisement

7-2. Operation Data
Outdoor Unit: RAS-3M26S3AV-E, -A, -TR
<Cooling>
No. of
Temperature condition
operating
units
Indoor
Outdoor
1 unit
2 units
27/19
35/-
3 units
NOTES:
1. Measure surface temperature of heat exchanger pipe around of heat exchanger path U bent. (Thermistor
thermometer)
2. Connecting piping condition : 5 meters × 3 units (5 m / each indoor unit)
Standard
Indoor unit
pressure
A
B
C
P (MP)
07
-
-
0.9 to 1.1
10
-
-
0.8 to 1.0
13
-
-
0.7 to 0.9
16
-
-
0.6 to 0.8
18
-
-
0.6 to 0.8
22
-
-
0.6 to 0.8
24
-
-
0.6 to 0.8
07
07
-
0.8 to 1.0
10
07
-
0.8 to 1.0
13
07
-
0.8 to 1.0
16
07
-
0.8 to 1.0
18
07
-
0.8 to 1.0
22
07
-
0.8 to 1.0
24
07
-
0.7 to 0.9
10
10
-
0.8 to 1.0
13
10
-
0.8 to 1.0
16
10
-
0.8 to 1.0
18
10
-
0.8 to 1.0
22
10
-
0.7 to 0.9
24
10
-
0.7 to 0.9
13
13
-
0.8 to 1.0
16
13
-
0.7 to 0.9
18
13
-
0.7 to 0.9
22
13
-
0.7 to 0.9
24
13
-
0.7 to 0.9
16
16
-
0.7 to 0.9
18
16
-
0.7 to 0.9
22
16
-
0.7 to 0.9
24
16
-
0.7 to 0.9
18
18
-
0.7 to 0.9
22
18
-
0.7 to 0.9
24
18
-
0.7 to 0.9
07
07
07
0.8 to 1.0
10
07
07
0.8 to 1.0
13
07
07
0.8 to 1.0
16
07
07
0.8 to 1.0
18
07
07
0.8 to 1.0
22
07
07
0.8 to 1.0
24
07
07
0.8 to 1.0
10
10
07
0.8 to 1.0
13
10
07
0.8 to 1.0
16
10
07
0.8 to 1.0
18
10
07
0.8 to 1.0
22
10
07
0.8 to 1.0
24
10
07
0.8 to 1.0
13
13
07
0.8 to 1.0
16
13
07
0.8 to 1.0
18
13
07
0.8 to 1.0
22
13
07
0.8 to 1.0
24
13
07
0.8 to 1.0
16
16
07
0.8 to 1.0
Heat exchanger
pipe temperature
T1 (ºC)
T2 (ºC)
15 to 17
36 to 42
12 to 14
36 to 42
10 to 12
36 to 44
9 to 11
36 to 46
10 to 12
36 to 47
8 to 10
36 to 47
8 to 10
36 to 47
10 to 12
47 to 49
10 to 12
47 to 49
10 to 12
47 to 49
10 to 12
47 to 49
10 to 12
47 to 49
10 to 12
49 to 51
9 to 11
51 to 53
10 to 12
47 to 49
10 to 12
47 to 49
10 to 12
49 to 51
10 to 12
49 to 51
9 to 11
51 to 53
9 to 11
51 to 53
10 to 12
47 to 49
9 to 11
51 to 53
9 to 11
51 to 53
9 to 11
51 to 53
9 to 11
51 to 53
9 to 11
52 to 54
9 to 11
52 to 54
9 to 11
52 to 54
9 to 11
52 to 54
9 to 11
52 to 54
9 to 11
52 to 54
9 to 11
52 to 54
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
11 to 13
51 to 53
- 36 -
FILE NO. SVM-15074
Indoor fan
Outdoor fan
High
LOW
High
MED
High
MED
High
MED
High
High
High
High
High
High
High
MED
High
MED
High
MED
High
MED
High
High
High
High
High
High
High
MED
High
MED
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
Compressor
revolution
(rps)
15.6
23.3
36.5
50.3
52.1
52.7
70.0
42.5
42.5
45.8
49.1
52.3
55.6
58.9
42.5
49.1
52.3
55.6
58.9
62.2
55.6
58.9
62.2
62.2
62.2
62.2
62.2
62.2
62.2
62.2
62.2
62.2
59.8
59.8
59.8
59.8
59.8
59.8
59.8
59.8
59.8
59.8
59.8
59.8
59.8
59.8
59.8
59.8
59.8
59.8
59.8

Hide quick links: