Samsung AC035JNMCEH Service Manual page 34

System air conditioner
Table of Contents

Advertisement

E. S. P(External Static Pressure) setting for phase control motor
With its phase control motor, you can adjust the indoor unit fan speed depending on the installation condition.
If the external static pressure is high so that the duct becomes longer or if the external static pressure is low so that
the duct becomes shorter, adjust the fan speed by referring the following table.
Model
Static Pressure(mmAq)
0≤ SP ≤2.5
2.5< SP ≤5
5< SP ≤7.5
7.5< SP ≤10
10< SP ≤12.5
12.5< SP ≤15
Model
Static Pressure(mmAq)
0≤ SP ≤4
4< SP ≤8
8< SP ≤12
12< SP ≤15
represents E. S. P(External Static Pressure) range of factory setting.
You don't have to adjust the fan speed separately if the external static pressure of the installation place is in
. When it is out of
• If you input the inappropriate option code, error may occur or the air conditioner is out of order. The
option code must be inputted correctly by the installation specialist or service agent.
4-8
AC035JNMCEH
01B26C-1C5081-27232B-371000
01B26C-1C50E6-27232B-371000
01B26C-1C545B-27232B-371000
01B26C-1C54CF-27232B-371000
01B26C-1C5933-27232B-371000
01B26C-1C5987-27232B-371000
AC100JNMCEH
01B26C-1C50F2-276470-375045
01B26C-1C5447-276470-375045
01B26C-1C54BC-276470-375045
01B26C-1C5910-276470-375045
, input the appropriate option code.
Option code for indoor unit
01B26C-1C50D5-274750-372020
01B26C-1C5459-274750-372020
01B26C-1C54BC-274750-372020
01B26C-1C54FE-274750-372020
01B26C-1C5942-274750-372020
01B26C-1C5994-274750-372020
Option code for indoor unit
01B26C-1C5425-277D8C-374045
01B26C-1C547A-277D8C-374045
01B26C-1C54ED-277D8C-374045
01B26C-1C5929-277D8C-374045
AC071JNMCEH
AC125JNMCEH
Samsung Electronics

Advertisement

Table of Contents
loading

Table of Contents