8.3 Precautions when charging refrigerant
8.4 To determine the additional refrigerant amount
8.5 To determine the complete recharge amount
8.6 To charge additional refrigerant
2(A)MXM40+50 + 2(A)MXF40+50
R32 Split series
4P600463-3D – 2021.03
INFORMATION
Also read the precautions and requirements in the following chapters:
▪
"2 General safety
▪
"7.1 Preparing refrigerant
If the total liquid piping
length is...
≤20 m
>20 m
INFORMATION
Piping length is the one-way length of liquid piping.
INFORMATION
If a complete recharge is necessary, the total refrigerant charge is: the factory
refrigerant charge (see unit name plate) + the determined additional amount.
WARNING
▪
Only use R32 as refrigerant. Other substances may cause explosions and
accidents.
▪
R32 contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 675. Do NOT vent these gases into the atmosphere.
▪
When charging refrigerant, ALWAYS use protective gloves and safety glasses.
CAUTION
To avoid compressor breakdown, do NOT charge more than the specified amount of
refrigerant.
Prerequisite: Before charging refrigerant, make sure the refrigerant piping is
connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to the service port.
2 Charge the additional refrigerant amount.
3 Open the gas stop valve.
precautions" [
4
5]
4
piping" [
33]
Do NOT add additional refrigerant.
R=(total length (m) of liquid piping–20 m)×0.020
R=Additional charge (kg) (rounded in units of 0.1 kg)
8
Charging refrigerant
|
Then...
Installer reference guide
47