Commissioning; Overview: Commissioning; Precautions When Commissioning - Daikin FCAHG100HVEB Manual

Table of Contents

Advertisement

If you want
Outdoor unit
General
(2)
During heating
LL
operation
Setup
(2)
volume
Setting: Time to clean air filter
This setting must correspond with the air contamination in the room.
It determines the interval at which the TIME TO CLEAN AIR FILTER
notification is displayed on the user interface. When using a wireless
user interface, you must also set the address (see the installation
manual of the user interface).
If you want an interval of...
(air contamination)
±2500 h (light)
±1250 h (heavy)
No notification
Individual setting in a simultaneous operation system
We recommend using the optional user interface to set the slave
unit.
Perform the following steps:
2 Change the second code number to 02 to perform individual
setting on the slave unit.
If you want to set the slave unit as...
Unified setting
Individual setting
3 Perform field setting for the master unit.
4 Turn off the main power supply switch.
5 Disconnect the remote controller from the master unit and
connect it to the slave unit.
6 Change to individual setting.
7 Perform field setting for the slave unit.
8 Turn off the main power supply or, in case of more slave units,
repeat the previous steps for all slave units.
9 Disconnect the user interface from the slave unit and reconnect
it to the master unit.
It is not necessary to rewire the remote controller from the master
unit if the optional user interface is used. (However, remove the
wires attached to the user interface terminal board of the master
unit)
(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• C1: First code number
• C2: Second code number
: Default
(2)
Fan speed:
• LL: Low fan speed
• Setup volume: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
• Monitoring 1, 2: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by Low fan speed (1) or by Setup
volume (2).
FCAHG71~140HVEB
Split system air conditioners
4P561449-1A – 2019.09
(1)
Then
M
C1
C2
3MXM, 4MXM,
5MXM
(2)
Monitoring 1
12
3
01
(22)
(2)
Monitoring 2
02
(1)
Then
M
C1
C2
10 (20)
0
01
02
3
02
(1)
Then
M
C1
C2
21(11)
01
01
02
1~ 50 Hz
220-240 V
c
d
A
B
a
e2
e1
A
Master unit
B
Slave unit
a
Interconnection cable
b
Power supply cable
c
Earth leakage circuit breaker
d
Fuse
e1
Main user interface
e2
Optional user interface
8

Commissioning

NOTICE
General
commissioning
commissioning instructions in this chapter, a general
commissioning checklist is also available on the Daikin
Business Portal (authentication required).
The general commissioning checklist is complementary to
the instructions in this chapter and can be used as a
guideline and reporting template during the commissioning
and hand-over to the user.
8.1

Overview: Commissioning

This chapter describes what you have to do and know to
commission the system after it is installed.
Typical workflow
Commissioning typically consists of the following stages:
1
Checking the "Checklist before commissioning".
2
Performing a test run for the system.
8.2

Precautions when commissioning

INFORMATION
During the first running period of the unit, the required
power may be higher than stated on the nameplate of the
unit. This phenomenon is caused by the compressor, that
needs a continuous run time of 50  hours before reaching
smooth operation and stable power consumption.
8 Commissioning
b
checklist.
Next
to
Installer and user reference guide
the
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcahg71hvebFcahg125hvebFcahg140hveb

Table of Contents