TROUBLESHOOTING (C0ntinued)
Symptom
Possible Cause
1.) System not set to Cool
2.) Loose connection to thermostat
or system
3.) Cooling System requires
service or thermostat requires
replacement
No Cool
Heat, Cool or Fan
Possible short in wiring, thermostat,
Runs Constantly
heat, cool or fan system
Thermostat
Display &
Thermostat display requires
Thermometer
adjustment
Disagree
Furnace (Air
Conditioner)
The location of the thermostat and/
Cycles Too Fast or
or the size of the Heating System
Slow (narrow or
may be influencing the cycle rate
wide temperature
swing)
1.) Heating system is not able to heat
the space to within 10 degrees of
the setpoint within 2 hours
2.) Cooling system is not able to cool
the space to within 10 degrees of
the setpoint within 2 hours
"Call for Service"
3.) If "--" is displayed for the Room
icon appears on
Temperature, a replacement
displayed
thermostat is needed
4.) None of the buttons operate on
the thermostat
5.) If "Call for Service" is flashing,
compressor self diagnostic is
detecting an issue with the
outdoor unit
Resetting the Thermostat or Thermostat Settings
If the thermostat has good batteries, but has a blank display or does not respond to key
presses, the thermostat should be reset by removing the batteries for 2 minutes. This reset
will not change the menu settings or program. If the condition persists after reinstalling the
batteries, replace the thermostat.
To conveniently reset only the schedule and user settings back to factory defaults, press Menu
and Backlight buttons at the same time and hold until the display goes blank and resets.
WARNING: This product contains a chemical known to the state of California to cause
cancer and birth defects and other reproductive harm.
HOMEOWNER HELP LINE: 1-800-284-2925
White-Rodgers is a business
of Emerson Electric Co.
The Emerson logo is a
trademark and service mark
of Emerson Electric Co.
Corrective Action
1.) Set thermostat to Cool.
2.) Verify thermostat and system wires are securely
attached.
3.) Diagnostic: Set System to Cool and lower
setpoint below room temperature. Same
procedures as diagnostic for "No Heat" condition
except set the thermostat to Cool and lower the
setpoint below the room temperature. There may
be up to a five minute delay before the thermostat
clicks in Cooling if the compressor lock-out option
is selected in the installer menu. (see INSTALLER
MENU, item 50)
Check each wire connection to verify they are not
shorted or touching other wires. Try resetting the
thermostat. If the condition persists contact your
HVAC service person.
Display can be adjusted +/-5°. See User Menu
item 05
Digital thermostats provide precise control and
cycle faster than older mechanical models. The
system turns on and off more frequently, but runs
for a shorter time. If you would like to increase
cycle time, choose SLO for slow cycle in the
Installer menu. (Reference menu items 30, 32 &
35) If an acceptable cycle rate is not achieved,
contact your HVAC service person.
1.) See corrective action for "No Heat"
2.) See corrective action for "No Cool"
3.) Replace thermostat
4.) Make sure keypad lockout is not turned on ( ),
If it's OFF, try reset shown below.
5.) Contact a service person to verify the outdoor
equipment is operating correctly
white-rodgers.com
emerson.com