OUTDOOR UNIT COMBINATION
• Make sure an indoor unit is compatible with DVM PLUS IV
• Indoor units can be connected within following table range.
• If the total capacity of the connected indoor units exceeds the suggested guideline, the indoor unit
cooling and heating capacity may decrease.
• Total capacity of the connected indoor units can be allowed to be from 50% to 130% over outdoor
capacity. (Depending on operation condition, the ratio of total capacity of the connected indoor units
over outdoor unit capacity should be considered carefully.)
0.5x∑ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3x∑ (Outdoor unit
capacity)
• Up to 64 indoor units can be connected to an outdoor unit. The communication address of the indoor
unit sets following the quantity of the maximum indoor unit connected.
• The minimum capacity of the indoor unit is 2.2kW.
• Make sure to follow the table for combination installation of outdoor units.
CAUTION
Type
Outdoor unit capacity (HP)
RD080HHXG
RD080HRXG
RD100HHXG
RD100HRXG
RD120HHXG
Outdoor unit combination
RD120HRXG
RD140HHXG
RD140HRXG
RD160HHXG
RD160HRXG
High
efficiency
Cooling[kW]
Nominal
capacity
Heating[kW]
Minimum[kW] 11.2 14.0 16.8 19.6 22.4 25.2 28.0 30.8 33.6 36.4 39.2 42.0 44.8 47.6 50.4 53.2 56.0 58.8 61.6 64.4 67.2
Total capacity of the connected
indoor units (cooling)
Maximum[kW] 29.1 36.4 43.7 51.0 58.2 65.5 72.8 80.1 87.4 94.6 101.9 109.2 116.5 123.8 131.0 138.3 145.6 152.9 160.2 167.4 174.7
Maximum number of connectable indoor
unit
RD080HHXG
RD080HRXG
RD100HHXG
RD100HRXG
RD120HHXG
RD120HRXG
RD140HHXG
Outdoor unit combination
RD140HRXG
RD160HHXG
RD160HRXG
RD180HHXG
RD180HRXG
Compact
RD200HHXG
RD200HRXG
Cooling[kW]
Nominal
capacity
Heating[kW]
Minimum[kW] 11.2 14.0 16.8 19.6 22.4 25.2 28.0 30.8 33.6 36.4 39.2 42.0 44.8 47.6 50.4 53.2 56.0 58.8 61.6 64.4 67.2 70.0 72.8 75.6 78.4 81.2 84.0
Total capacity of the connected
indoor units (cooling)
Maximum[kW] 29.1 36.4 43.7 51.0 58.2 65.5 72.8 80.1 87.4 94.6 101.9 109.2 116.5 123.8 131.0 138.3 145.6 152.9 160.2 167.4 174.7 182.0 189.3 196.6 203.8 211.1 218.4
Maximum number of connectable indoor unit
8
10
12
14
16
18
20
22
24
1
1
1
1
1
2
1
2
1
1
1
22.4 28.0 33.6 39.2 44.8 50.4 56.0 61.6 67.2 72.8 78.4 84.0 89.6 95.2 100.8 106.4 112.0 117.6 123.2 128.8 134.4
25.2 31.5 37.8 44.1 50.4 56.7 63.0 69.3 75.6 81.9 88.2 94.5 100.8 107.1 113.4 119.7 126.0 132.3 138.6 144.9 151.2
13
17
20
23
26
30
33
36
40
1
1
1
1
1
2
1
1
1
1
22.4 28.0 33.6 39.2 44.8 50.4 56.0 61.6 67.2 72.8 78.4 84.0 89.6 95.2 100.8 106.4 112.0 117.6 123.2 128.8 134.4 140.0 145.6 151.2 156.8 162.4 168.0
25.2 31.5 37.8 44.1 50.4 56.7 63.0 69.3 75.6 81.9 88.2 94.5 100.8 107.1 113.4 119.7 126.0 132.3 138.6 144.9 151.2 157.5 163.8 170.1 176.4 182.7 189.0
13
17
20
23
26
30
33
36
40
26
28
30
32
34
36
38
40
42
1
1
2
1
1
1
1
2
1
1
1
1
1
1
2
1
1
1
1
1
43
46
50
53
56
60
63
64
64
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
43
46
50
53
56
60
63
64
64
preparing the installation _07
44
46
48
50
52
54
56
58
60
1
1
2
2
3
64
64
64
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
3
64
64
64
64
64
64
64
64
64