installing the unit
REFRIGERANT PIPING WORKS
Pipe selection for DVM PLUS IV HR
12HP
14HP
16HP
(E)
(A1)
(A1)
(A1)
(A2)
(A3)
(F)
(D)
•
Example) 42HP of compact
combinations
Pipe size
(O. D.mm)
HP Mark
Liquid Low
gas
12
(A1)
Ø12.70
Ø25.40 Ø22.23
14
(A1)
Ø12.70
Ø25.40 Ø22.23
16
(A1)
Ø12.70
Ø28.58 Ø22.23
26
(A2)
Ø19.05
Ø31.75 Ø28.58
42
(A3)
Ø19.05
Ø38.10 Ø31.75
The sum of the total capacity of the indoor units connected to a MCU should not be over
the max. 44.8kW.
CAUTION
18_ installing the unit
Outdoor unit connection pipe size : (A1), (A2), (A3)
A1 : Select the pipes according to the outdoor
unit capacity with following table.
A2 : Select the pipes according to sum of
outdoor unit capacities behind the outdoor
joint with following table.
A3 : Select the main pipe of outdoor units with
the following table.
Pipe size (O.D. mm), (A)
Outdoor
unit
Liquid Gas
(B)
8HP
Ø9.52
10HP
12HP
14HP
Ø12.70
16HP
18HP
(C)
20HP
Ø15.88
22HP
24HP
26~30HP
32~34HP
Ø19.05
36~48HP
50~60HP Ø22.23 Ø44.45 Ø38.10
High
*A1 : Pipes to the outdoor unit (Liquid, Gas, High pressure gas)
gas
*A2 : Pipes between outdoor joint kits
(Liquid, Gas, High pressure gas)
*A3 : Main pipes (Liquid, Gas, High pressure gas)
Pipe size between branch joints : (B)
Select the pipe size according to the capacity sum of
indoor units which are connected below this pipe.
Total indoor unit's
capacity
15.0kW and below
Over 15.0~23.2kW and below
Over 23.2~29.0kW and below
Over 29.0~40.6kW and below
Over 40.6~46.4kW and below
Over 46.4~69.6kW and below Ø15.88
Over 69.6~98.6kW and below
Over 98.6~139.2kW and below
Over 139.2kW
Pipe size between branch joints and indoor unit : (C)
Select the pipe size according to the indoor
unit's capacity.
Indoor unit's
capacity
2.2~5.6kW
7.1~14.0kW
Oil
balancing
High
pipe size
gas
Ø19.05 Ø15.88
Ø22.23 Ø19.05
Ø25.40
Ø22.23
Ø28.58
Ø6.35
Ø25.40
Ø31.75 Ø28.58
Ø38.10 Ø31.75
Pipe size (O.D. mm)
High
Liquid Gas
gas
Ø15.88
Ø15.88
Ø9.52
Ø19.05
Ø22.23 Ø19.05
Ø25.40
Ø12.70
Ø22.23
Ø28.58
Ø25.40
Ø31.75 Ø28.58
Ø19.05
Ø38.10 Ø31.75
Ø22.23 Ø44.45 Ø38.10
Pipe size (O. D. mm)
Liquid
Gas
Ø6.35
Ø12.70
Ø9.52
Ø15.88
Branch joint : (D), (E), (F)
Branch joint of outdoor unit's multi
connection (D)
Model
Liquid & Low
MXJ-T3819
gas pipe
MXJ-T4422
MXJ-T3100
High gas pipe
MXJ-T3800
First branch joint (E)
Select branch joint according to outdoor
unit's capacity.
Outdoor unit
Liquid
8~14HP
& Low
16HP
pressure
18~24HP
gas
26~34HP
Y-joint
(E)
36~48HP
50~60HP
Outdoor unit
High
8HP
pressure
gas
10~24HP
Y-joint
26~48HP
(E)
50~60HP
Branch joint (F)
Total indoor unit's
Model
MXJ-YA1509 15.0kW and below
Liquid
& low
MXJ-YA2512 Over 15.0~40.6kW and below
pressure
MXJ-YA2812 Over 40.6~46.4kW and below
gas
MXJ-YA2815 Over 46.4~69.6kW and below
Y-joint
(F)
MXJ-YA3119 Over 69.6~98.6kW and below
MXJ-YA3819 Over 98.6~139.2kW and below
MXJ-YA4422 Over 139.2kW
Total indoor unit's
Model
High
pressure
MXJ-YA1500 23.2kW and below
gas
MXJ-YA2500 Over 23.2~69.6kW and below
Y-joint
(F)
MXJ-YA3100 Over 69.6~139.2kW and below
MXJ-YA3800 Over 139.2kW
Capacity of
outdoor
Below 48 HP
Above 50 HP
Below 48 HP
Above 50 HP
Model
MXJ-YA2512
MXJ-YA2812
MXJ-YA2815
MXJ-YA3119
MXJ-YA3819
MXJ-YA4422
Model
MXJ-YA1500
MXJ-YA2500
MXJ-YA3100
MXJ-YA3800
capacity
capacity