CAUTION
!
1
Install declination of the indoor unit is very important for the drain of the duct type air
conditioner.
2
Minimum thickness of the insulation for the connecting pipe shall be 5mm.
Front of view
• The unit must be declined to the drain hose connected when finished installation.
CORRECT
Drainage hole
CAUTION FOR GRADIENT OF UNIT AND DRAIN PIPING
Lay the drain hose with a downward inclination so water will drain out.
• Always lay the drain with downward
inclination (1/100 to 1/50).
Prevent any upward flow or reverse flow
in any part.
• 10mm or thicker formed thermal insulator
shall always be provided for the drain
pipe.
Unit
Make sure to be closed.
CORRECT
Ceiling
INCORRECT
Thermal insulator
(Local supply)
Drainage pipe
(Local supply)
Drainage hole
THE INDOOR UNIT INSTALLATION
Drainage hole
• Upward routing not allowed
INCORRECT
• Install the P-Trap (or U-Trap) to prevent
a water leakage caused by the blocking
of intake air filter.
Applied U-Trap Dimension
A
70mm
B
2C
C
2 x SP
SP = External Pressure
(mmAq)
Ex) External Pressure
= 10mmAq
A
70mm
B
40mm
C
20mm
9
B
C
U-Trap