Advertisement

5.3. f830: Assembly Object Setting

The Input/Output Instance of DEV002Z is set up by this parameter.
The DEV002Z supports both the standard DeviceNet AC Drive profile Instances 20/70,
21/71 and user defined Instances 100/150, 101/151, 102/152.
* For an explanation of f830 = 0 (Instance 20/70), 1 (Instance 21/71), 3 (Instance
101/151) and 4 (Instance 102/152), refer to the function manual (E6581281).
f830=2 (Instance 100/150)
Byte
0
Command
1
2
3
Byte
0
1
(Reserved)
2
3
*
Drive Reference Speed
A frequency should be specified in hexadecimal notation in units of 0.01Hz.
For example, to set the frequency at 60Hz, since the minimum unit of frequency is
0.01Hz, you have to enter the following number.
60÷0.01 = 6000 = 0x1770 (hexadecimal)
bit7
bit6
DC
Acc./Dec.
PI control
braking
#1/#2
Frequency
Reset
link
link
bit7
bit6
DC
Acc./Dec.
PI control
braking
#1/#2
READY
READY
without
with
ST/RUN
ST/ RUN
command value
bit5
bit4
bit3
Motor
Preset
#1/#2
Speed 4
Emerg.
Free run
trip
stop
(ST)
Drive Reference Speed Hz (Low byte)
Drive Reference Speed Hz (High byte)
Output Instance 100 format
bit5
bit4
bit3
Motor
(Reserved)
#1/#2
Emerg.
Free run
stop
(ST)
Drive Actual Speed Hz (Low byte)
Drive Actual Speed Hz (High byte)
Input Instance 150 format
- 15 -
E6581295⑥
bit2
bit1
Preset
Preset
Preset
Speed 3
Speed 2
Speed 1
Forward/
Run/Stop
Reverse
bit2
bit1
ALARM
Fault
Fault FL
(fc91)
Forward/
Run/Stop
Reverse
bit0
Jog
bit0
Jog