Exterior Features; Devicenet Connector - Toshiba DEV002Z Instruction Manual

Devicenet option
Hide thumbs Also See for DEV002Z:
Table of Contents

Advertisement

2. Exterior features

The external view of this option and the name of each part are shown below:
DeviceNet indicator
(Refer to Section 2.2)
Prohibited

2.1. DeviceNet connector

Used to connect DeviceNet network cables. The terminal is a plug-type and the signal of each
terminal is as follows.
Size of connectable wire: 0.3 to 1.5mm
Tightening torque: 0.5 to 0.6 N·m
Recommended screwdriver: Small flat-blade screwdriver (blade thickness: 0.6mm, blade width:
3.5mm or less)
DeviceNet connector
(Refer to Section 2.1)
▼ Do not change the switch setting when the power is on.
It could lead to electric shocks, or the option might breaks down or get
damaged.
- 7 -
Dip switch
(Refer to Section 4.3)
Danger
Color
Symbol
Red
V+
Network Power Supply (V+)
White
CAN_H
Communication signal (High)
Silver
SHIELD
Shield
Blue
CAN_L
Communication signal (Low)
Black
V-
Network Power Supply (V-)
2
(AWG 22 to 16), Strip-off length: 7mm
E6581295⑥
Panel mounting tabs
(Refer to Section 3)
Signal classification: