4. Connecting to the network

4.1. Installation method

(1) Attach DeviceNet cable to DeviceNet connector. (Refer to Section 2.1).
(Be careful not to short-circuit adjacent terminals on DeviceNet connector).
<Recommended cable>
<Tightening torque>
(2) Please set the terminating resistance if needed.
<Terminating resistance specification>
(3) Using the DIP switch on the DeviceNet
(Refer to Section 4.3).
(4) Once all the parameters are set, the power must be cycled to the VF-AS1/PS1 for
these changes to take effect. (Refer to Section 5.)
Thin branch cables: DeviceNet-specific thin cable.
0.5 - 0.6 N·m
Recommended screwdriver: Small flat-blade screwdriver (blade thickness: 0.6mm,
blade length: 3.5mm or less)
1/4 W - 121 ohm, 1% Metal Film
, set a MAC ID number and a baud rate.