How Releasing Zones Operate
Cross Zone Selection
(Cross=)
Cross=ZONE
Cross=HEAT
NFS2-3030 Operations Manual — P/N 52546:A 11/29/2005
Condition(s) Required to Activate the Releasing zone
An alarm from two detectors mapped to different Software Zones, but
mapped to the same Releasing Zone.
• An alarm from L02D101 and L02D103 – detectors mapped to
different zones, but both list ZR01 in their zone map.
• An alarm from L02D102 and L02D104 – detectors mapped to
different zones, but both list ZR01 in their zone map.
• An alarm from L02D101 and L02D104 – detectors mapped to
different zones, but both list ZR01 in their zone map.
• An alarm from L02D102 and L02D103 – detectors mapped to
different zones, but both list ZR01 in their zone map.
Activation of heat detector L02D104 and one smoke detector
(L02D101, L02D102, or L02D103).
Table B.2 Example of Cross Zone Selections