Operating Features
the Local Control option is disabled, the panel does not have local control of the Signal Silence,
System Reset, and Drill Fixed Function keys, or the SIGNAL SILENCE, SYSTEM RESET, and
ACKNOWLEDGE soft keys. These functions must be performed by a remote device
preprogrammed for this purpose. When this panel is not the DCC on a network, permission must
be granted from the DCC before Signal Silence, System Reset, Acknowledge or Drill can be
performed at this panel. Pressing one of these keys will automatically send a permission request
to the DCC.
Keypad
The alphanumeric portion of the keypad is in standard QWERTY format. This keypad is functional
mainly when an entry is requested by the system. Otherwise, pressing these keys results in no entry.
Soft Keys
The ten keys to the right and left of the display function to select commands that appear on the
display. Each screen has different information, and each key changes function to suit the screen.
Beneath each screen in this manual is a description of the function of each soft key.
Fixed Function Keys
The nine keys aligned along the upper right edge of the keypad/display are fixed function keys.
ACKNOWLEDGE - Press this key to acknowledge an off-normal event displayed on the screen.
FIRE ALARM
SECURITY
SUPERVISORY
TROUBLE
OTHER EVENT
SIGNAL SILENCE - Press this key to turn off all control modules and panel output circuits that
have been programmed as silenceable. Signal Silence is disabled while the Silence Inhibit Timer is
in effect, or when a device with a Waterflow type code initiates a fire alarm.
DRILL
HOLD 2 SEC.
output circuits.
SYSTEM RESET - Press this key to clear all latched alarms and other events as well as turn off
event LEDs. If alarms or other off-normal events exist after reset, they will resound the system and
relight the LEDs. Unacknowledged events will not prevent reset from functioning unless the panel
is programmed for Receive Mode (refer to the note on page page 24). The SYSTEM RESET key
will not function if the programmable Silence Inhibit Timer is running.
The System Reset key will not immediately silence active outputs. If the Control-by-event programming
conditions for the output are not met after reset, the output will deactivate. (Typically 30 seconds local,
60 seconds network.)
Special Function Keys
To the right of the QWERTY keypad are special function keys.
Arrow Keys - Pressing these keys navigates through the programming fields on a display screen by
advancing or reversing the cursor position.
Enter - Pressing this key navigates through the programming fields on a display screen by
advancing the cursor.
Esc - Press this key once to leave the current field without saving the entry. Press this key twice in
succession to discard any changes made on the screen and exit to the previous screen.
DISABLE/ENABLE - For future use. No function at this time.
NFS2-3030 Operations Manual — P/N 52546:A 11/29/2005
SCROLL/DISPLAY
SCROLL/DISPLAY
SCROLL/DISPLAY
SCROLL/DISPLAY
SCROLL/DISPLAY
- Press this key, holding it down for 2 seconds, to activate all silenceable fire
Scroll through a list of events of these types,
each of which will appear on the display once
the associated button is pushed. The OTHER
EVENT
SCROLL/DISPLAY
between prealarm and disabled events.
General Information
key also scrolls
11