Honeywell NOTIFIER NFS2-3030 Operation Manual page 18

Fire alarm control panel
Hide thumbs Also See for NOTIFIER NFS2-3030:
Table of Contents

Advertisement

General Information
Display
Lines 1 through 4 - Event information
Line 5 - Screen title
Lines 6 through 9 - The Custom Action Message programmed for the point in alarm
Line 10 - blank
Line 11 and 14 - These lines exist only for smoke/heat detectors. They do not display for
wireless smoke detectors.
Line 11
V A L U E S
The screen displays the Alarm and Prealarm values that are in effect when more information is
requested. For example, if occupied settings are in effect, occupied values will display.
1 2 1 % O F A L A R M -
alarm level value (indicated in the next line on the screen). The example above shows the
detector exceeding the alarm level by 21%.
Note: For Beam detectors in CLIP mode, the alarm value will always equal zero (0)% when it
is not in alarm or 100% when it is in alarm.
1 4 5 % O F P R E A L A R M -
preprogrammed prealarm level value (indicated in the next line on the screen). The example
above shows the detector exceeding the prealarm level by 45%.
Line 12
The screen displays the Alarm and Prealarm levels that are in effect when more information is
requested. For example, if unoccupied settings are in effect, they will display.
A L A R M : 6 = 1 . 6 6 % -
value is 1.66%, indicating the percent per foot obscuration value assigned to level 6.
P R E A L A R M : 3 = 0 . 4 7 % -
its value is 0.47%, indicating the percent per foot obscuration value assigned to level 3.
Line 13
A C T I O N / S T A T U S : N O N E / V E R Y C L E A N -
the device. The message that appears in this field depends on the drift compensation value. A
detector will automatically compensate for environmental contaminants and other factors over
time, until the tolerance value has been exceeded. The FACP will signal a trouble condition
when this level has been reached. Refer to the following table for messages and required
action.
Line 13 does not display for Acclimate detectors.
18
:
This field gives the detector reading as it relates to its preprogrammed
This field gives the detector reading as it relates to its
Six is the preprogrammed alarm level value for this detector: its
Three is the preprogrammed alarm level value for this detector:
Message
Replace/Malfunction
None/Very Clean
None/Clean
None/Fairly Clean
Needs Cleaning
Needs Immediate Cleaning
This displays the maintenance status of
Description
Replace the defective detector. The detector may not
operate properly.
No action necessary. The detector readings are near ideal.
No action necessary. Although not ideal, the detector will
activate at the selected sensitivity level.
No action necessary. The detector will activate at the
selected sensitivity level.
Clean the detector soon. The detector may cause a false
alarm because it has reached the drift compensation
tolerance value.
Clean immediately! The detector is a false alarm risk. The
drift compensation tolerance value has been exceeded.
NFS2-3030 Operations Manual — P/N 52546:A 11/29/2005