7 Press the center button to go back to the home
screen.
INFORMATION
When you change the overview settings and you go back
to the home screen, the user interface will show a popup
screen and request to restart the system.
When confirmed, the system will restart and recent
changes will be applied.
8.2

Configuration wizard

After first power ON of the system, the user interface starts a
configuration wizard. Use this wizard to set the most important initial
settings for the unit to run properly. If required, you can afterwards
configure more settings. You can change all these settings via the
menu structure.
8.2.1

Configuration wizard: Language

#
Code
[7.1]
N/A
Language
8.2.2

Configuration wizard: Time and date

#
Code
[7.2]
N/A
Set the local time and date
INFORMATION
By default, daylight savings time is enabled and clock
format is set to 24 hours. These settings can be changed
during initial configuration or via the menu structure [7.2]:
User settings > Time/date.
8.2.3

Configuration wizard: System

Backup heater type
▪ For models with integrated backup heater, this is fixed to 3V.
▪ For other models, this can be set to No heater, or External
heater (i.e. when the optional external backup heater kit is
installed).
#
Code
[9.3.1]
[E‑03]
▪ 0: No heater
▪ 1: External heater
▪ 2: 3V
Domestic hot water
The following setting determines if the system can prepare domestic
hot water or not, and which tank is used. Set this setting according to
the actual installation.
EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3
Daikin Altherma 3 M
4P685229-1A – 2022.05
Description
Description
Description
#
Code
(a)
[9.2.1]
[E‑05]
▪ No DHW
(a)
[E‑06]
No tank installed.
(a)
[E‑07]
▪ EKHWS/E, small volume
Tank with booster heater installed at
the side of the tank, with a volume of
150 l or 180 l.
▪ EKHWS/E, big volume
Tank with booster heater installed at
the side of the tank, with a volume of
200 l, 250 l or 300 l.
▪ EKHWP/HYC
Tank with optional booster heater
installed at the top of the tank.
▪ 3rd party, small coil
Third-party tank with a coil size larger
than 1.05 m².
▪ 3rd party, big coil
Third-party tank with a coil size larger
than 1.80 m².
(a)
Use the menu structure instead of the overview settings. Menu
structure setting [9.2.1] replaces the following 3 overview settings:
• [E-05]: Can the system prepare domestic hot water?
• [E-06]: Is a domestic hot water tank installed in the system?
• [E-07]: What kind of domestic hot water tank is installed?
In case of EKHWP, we recommend to use the following settings:
#
Code
Item
[9.2.1] [E‑07]
Tank type
N/A
[4-05]
Thermistor type
[5.8]
[6-0E]
Maximum tank
temperature
In case of EKHWS*D* / EKHWSU*D*, we recommend to use the
following settings:
#
Code
Item
[9.2.1] [E‑07]
Tank type
N/A
[4-05]
Thermistor type
[5.8]
[6-0E]
Maximum tank
temperature
In case of a third-party tank, we recommend to use the following
settings:
#
Code
Item
[9.2.1] [E‑07]
Tank type
N/A
[4-05]
Thermistor type
[5.8]
[6-0E]
Maximum tank
temperature
Emergency
When the heat pump fails to operate, the backup heater and/or
booster heater can serve as an emergency heater. It then takes over
the heat load either automatically or by manual interaction.
▪ When Emergency is set to Automatic and a heat pump failure
occurs, the backup heater automatically takes over the heat load,
and the booster heater in the optional tank takes over the
domestic hot water production.
8 Configuration
Description
EKHWP
5: EKHWP/HYC
0: Automatic
≤70°C
EKHWS*D* / EKHWSU*D*
150/180
200/250/300
0: EKHWS/E,
3: EKHWS/E,
small volume
big volume
0: Automatic
≤60°C
≤75°C
Third-party tank
Coil≥1.05 m²
Coil≥1.8 m²
7: 3rd party,
8: 3rd party,
small coil
big coil
0: Automatic
≤60°C
≤75°C
Installation manual
31