Configuration With The Configuration Menu; Fig. 108: Pt2006-A1 Configuration Buttons - Siemens Cerberus PACE Manual

Hide thumbs Also See for Cerberus PACE:
Table of Contents

Advertisement

7
Connect external components
Remote control panel PT2006-A1

7.14.2 Configuration with the configuration menu

168 | 173
The PT2006-A1 provides a configuration menu to change the following:
The brightness of the display
The RS485 ID
The RS485 ID must be set to the correct value to identify the component on the
'PACE-Bus' (RS485).
The ID must be unique on one 'PACE-Bus' (RS485).
1
2
4
5

Fig. 108: PT2006-A1 configuration buttons

Perform the following steps to change the RS485 ID and the brightness:
1. Press button 1 and 6 at the same time to enter the configuration menu.
 The RS485 ID is displayed.
2. Press button 6 (cfg) to change the configuration.
 The values for the RS485 ID and the brightness are displayed.
Button 2 - change between the RS485 ID and the brightness configuration
Button 1 - change the values, count down
Button 3 - change the values, count up
Button 4 - quit - leave configuration menu without saving the changes
Button 6 - save - save changes and leave the configuration menu
3
6
A6V10430579_en--_b

Advertisement

Table of Contents
loading

Table of Contents