Installation Procedure
NOTE
• If the pipes must be shortened, see Step 6 Cutting
and flaring the pipes on page 14.
2 Be sure to use an insulator thick enough to cover the
refrigerant pipes to improve the efficiency of the unit
and to prevent condensate water formation on the
outside of the pipes falling onto the floor.
3 Cut off any excess foam insulation.
4 Make sure that there are no cracks or waves on the
bent area.
5 It is necessary to double the insulation thickness
(0.39inch or more) to prevent condensation on the
insulator when the installed area is warm and humid.
6 Do not use joints or extensions for the pipes
connecting the indoor and outdoor units. The only
permitted connections are those for which the units
are designed.
CAUTION
• Connect the indoor and outdoor units using pipes
with flared connections (not supplied). For the lines,
use insulated, unwelded, degreased and deoxidized
copper pipe (Cu DHP type to ISO 1337 or UNI EN
12735-1), suitable for operating pressures of at least
4.2MPa (609.2 psig) and for a burst pressure of at least
20.7MPa (3002.3 psig). Copper pipe for hydro-sanitary
applications is completely unsuitable.
• For sizing and limits (height difference, line length,
max. bends, refrigerant charge, etc.) see the outdoor
unit installation manual.
• All refrigerant connection must be accessible, in order
to permit either unit maintenance or removing it
completely.
• If the pipes require brazing, make sure that oxygen
free nitrogen (OFN) is flowing through the system.
• Nitrogen blowing pressure range is 0.02 to 0.05 MPa
(2.9 to 7.3 psig).
16
English
DB68-11272A-00_IM_CAC WindFree1,4way_AA_EN_.indd 16
DB68-11272A-00_IM_CAC WindFree1,4way_AA_EN_.indd 16

Step 8 Performing the gas leak test

To identify potential gas leaks on the indoor unit, inspect
the connection area of each refrigerant pipe using a leak
detector for R-410A.
Before creating a vacuum and adding refrigerant,
pressurize the whole system with nitrogen using a
cylinder with a pressure reducer at a pressure above
4.1MPa (594.7 PSI) in order to detect leaks on the
refrigerant fittings.
Made vacuum for 15 minutes and pressurizing system
with nitrogen.
1 way Cassette
Insulator
4 way Cassette
Insulator
Liquid side
Gas side
Liquid side
Gas side