Procedure Of Fan Unit Replacement - Omron NX Series User Manual

Machine automation controller
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

Appendices
A-1 Specifications
This section gives the specifications of the NX-series CPU Units.
Enclosure
Grounding method
Dimensions (height × depth × width)
Weight
Current consumption
Operating envi-
ronment
Battery
Applicable
*1
standards
*1.
Refer to the OMRON website (http://www.ia.omron.com) or consult your OMRON representative for the
most recent applicable standards for each model.
A-2
Item
Ambient operating temperature
Ambient operating humidity
Atmosphere
Ambient storage temperature
Altitude
Pollution degree
Noise immunity
Overvoltage category
EMC immunity level
Vibration resistance
Shock resistance
Life
Model
EU Directives
cULus
Shipbuilding Standards
Other than the above.
NX7-££££
Mounted in a panel
Ground to less than 100 Ω.
100 mm × 100 mm × 132 mm
880 g (including the End Cover)
40 W (including SD Memory Card and End Cover)
0 to 55°C
10% to 95% (with no condensation)
Must be free from corrosive gases.
-25 to 70°C (excluding battery and Fan Unit)
2,000 m max.
2 or less: Meets IEC 61010-2-201.
2 kV on power supply line (Conforms to IEC
61000-4-4.)
Category II: Meets IEC 61010-2-201.
Zone B
Conforms to IEC 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, ac-
2
celeration of 9.8 m/s
100 min each in X, Y, and Z directions (10 sweeps of
10 min each = 100 min total)
Gravity acceleration is assumed to be G=9.8m/s
Conforms to IEC 60068-2-27.
2
147 m/s
, 3 times in X, Y, and Z directions
Gravity acceleration is assumed to be G=9.8m/s
2.5 years (at 25°C, Power ON time rate 0% (power
OFF))
CJ1W-BAT01
EN61131-2
Listed UL508 and ANSI/ISA 12.12.01
NK, LR
KC
NX-series CPU Unit Hardware User's Manual (W535)
2
.
2
.

Advertisement

Table of Contents
loading

Table of Contents