4 Installation and Wiring
Precautions for Grounding
• To prevent electrical shock, do not connect devices to ground poles (or steel frames) with non-
equalized potential to which multiple devices are connected.
• Use a ground pole as close to the Controller as possible and keep the ground line as short as possi-
ble.
• If the same ground is used for both the signal lines and the enclosure, isolate the channel base (a
grounded metal plate inside a control panel) with an insulating material.
Refer to Isolating the CPU Rack from the Control Panel on page 4-34 for how to isolate the NX-
series Controllers.
Example: Insulating and Grounding an Enclosure
• If high-frequency equipment is present, then ground not only the high-frequency equipment but also
the panel itself in which the Controller is housed.
• As shown in the following diagram, when using shielded cable for I/O wiring, connect the shield near
the Controller to the enclosure ground terminal.
Follow the instructions in the Communications Unit manual for preparing shielded communications
cable.
4-46
Insulating material
Channel base
Controller
Input
Output
Common
Common
Shielded Cable Ground
NX-series CPU Unit Hardware User's Manual (W535)