UNIT
ELECTRICAL
PA1Z
CHARACTERISTICS
060
230-1-60, 208/230-3-60, 460-3-60
Fig. 4 — Base Unit Dimensions, PA1Z060
REQUIRED CLEARANCES TO COMBUSTIBLE MAT'L — mm (in.)
Top of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Duct Side of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Bottom of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
NEC REQUIRED CLEARANCES — mm (in.)
Between Units, Power Entry Side . . . . . . . . . . . . . 1066.8 (42.00)
Unit and Ungrounded Surfaces, Power
Entry Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 914.0 (36.00)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Power Entry Side . . . . . . . . . 1066.8 (42.00)
REQUIRED CLEARANCES FOR SERVICING — mm (in.)
Condenser Coil Access Side . . . . . . . . . . . . . . . . . 762.0 (30.00)
Power Entry Side . . . . . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)
(Except for NEC Requirements)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 914.0 (36.00)
Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)
LEGEND
NEC — National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from
outdoor-fan discharge, with the exception of the condenser coil
(914 mm [36 in.]). A removable fence or barricade requires no
clearance.
2. Dimensions are in millimeters. Dimensions in ( ) are in inches.
UNIT WT
CENTER OF GRAVITY — mm (in.)
lb
kg
X
350
159
355.6 (14.00)
—4—
Y
Z
508.0 (20.00)
355.6 (14.00)