Trane YSJ072A Installation, Operation And Maintenance Manual page 26

Packaged rooftop air conditioners precedent cooling and gas/ electric
Table of Contents

Advertisement

Dimensions and Weights
Clearances
Figure 25, p. 26
illustrates the minimum operating and
service clearances for either a single or multiple unit
installation. These clearances are the minimum distances
necessary to assure adequate serviceability, cataloged unit
Figure 25.
Typical installation clearances for single and multiple unit applications
Side by Side
Note 1
Notes:
1. When equipped with economizer
or barometric relief damper, clearance
distance is to be measured from
protruding hood instead of base.
2. Clearance is the same if any unit
is rotated 180°.
3. Addition clearance required when
barometric damper or economizer
is installed.
Note 3
26
6'0"
1829 MM
7'0"
2134 MM
3'0"
914 MM
4'0"
for D cabinet
1219 MM
Single Unit
Barometric Relief Hood
7-3/4"
[198]
12"
[303]
Dimensions Extends to 21-5/8" (549 mm)
when Powered Exhaust is Coupled
with Low Leak Economizer
capacity, and peak operating efficiency. Providing less than
the recommended clearances may result in condenser coil
starvation, "short-circuiting" of exhaust and economizer
airflows, or recirculation of hot condenser air.
End to End
Note 1, 2
4'0"
1219 MM
5'0"
for D cabinet
1525 MM
3'0"
914 MM
3'0"
914 MM
Economizer Hood
7-1/4"
16-3/4"
[185]
[424]
RT-SVX071A-EN