Powerware BD User Manual page 16

Web/snmp card
Table of Contents

Advertisement

Local Configuration
3. Open your terminal emulation program such as
HyperTerminal and select the appropriate serial
connection (such as COM1).
The serial line should be set to 9600 baud, No parity,
8 data bits, 1 stop bit, and no flow control.
4. Verify that the UPS is turned on.
5. After a few seconds, press [Enter]. The Password
screen appears (see Figure 5).
If the screen does not appear, press [Enter] again.
If you still do not see the Password screen, check the
following conditions:
: Verify the serial line is set to 9600 baud, No parity,
8 data bits, 1 stop bit, and no flow control.
: If the serial line settings are correct, check the
cabling to verify all connections are secure.
: Verify that your terminal program is on the correct
communication port for the serial connection.
: Verify that the ConnectUPS Web/SNMP Card has
power (one or more LEDs on the card should be
illuminated). The UPS should be turned on.
6. Type your password (the default password is admin)
and press [Enter]. The Main Menu screen appears.
+===================================================================
|
[ ConnectUPS Web/SNMP Card Configuration Utility ]
+===================================================================
Enter Password: *****
+===================================================================
|
[ ConnectUPS Web/SNMP Card Configuration Utility ]
+===================================================================
1. Web/SNMP Card Settings
2. Reset Configuration to default
3. Restart Web/SNMP Card
4. UPS Pass-Through
0. Exit
Please Enter Your Choice =>_
Figure 5. ConnectUPS Web/SNMP Card Main Menu Screen
10
ConnectUPS
Web/SNMP Card (X and BD Models) User's Guide
:
Rev A www.powerware.com

Advertisement

Table of Contents
loading

This manual is also suitable for:

Connectups bdConnectups x

Table of Contents