American Standard CUX1B040A9241A Installation, Operation And Maintenance Manual page 17

Upflow / horizontal* and downflow / horizontal*, single stage direct vent gasfired condensing furnaces
Table of Contents

Advertisement

HORIZONTAL VENTING
NOTE:
Vent termination kit BAYAIR30AVENTA or BAYVENT200* may
be used instead of the horizontal and vertical termination
options shown in the following figures. For Canadian applica-
tions ONLY: IPEX 196006 may be used for horizontal and
vertical terminations. IPEX 081216, IPEX 081218, and IPEX
081219 may only be used for horizontal vent terminations.
!
When the vent pipe is exposed to temperatures below freezing,
i.e., when it passes through unheated spaces, etc., the pipe
must be insulated with 1/2 inch (22.7 mm) thick Armaflex-type
insulation or equal. If the space is heated sufficiently to prevent
freezing, then the insulation would not be required. If domestic
water pipes are not protected from freezing then it is assumed
the space meets the condition of a heated space.
HORIZONTAL VENTING THROUGH WALL
These furnaces may be installed as direct vent (as shipped)
or as nondirect vent. Installation must conform to national,
state, and local codes.
The vent & inlet terminals must be located at least 12" minimum
above normally expected snow accumulation level (18" minumum
in Canadian applications).
Avoid areas where staining or condensate drippage may be a
k
3.2"
COMBUSTION
AIR
BAYVENT200B
For Canadian applications only, IPEX 196006, IPEX 081216, IPEX 081218,
and IPEX 081219 may be used for horizontal vent terminations.
problem.
Location of the vent/wind terminal should be chosen to meet the
requirements of Figure 26 for either direct or non-direct vent
applications.
PITCH – Venting through the wall must maintain 1/4" per foot
pitched upward to insure that condensate drains back to the
furnace.
FLUE GAS DEGRADATION – The moisture content of the flue
gas may have a detrimental effect on some building materials.
This can be avoided by using the roof or chimney terminal, venting
option. When wall venting is used on any surface that can be
affected by this moisture, it is recommended that a corrosion
resistant shield (24 inches square) be used behind the vent
terminal. This shield can be wood, plastic, sheet metal, etc. Also,
silicone caulk all cracks, seams and joints within 3 feet of the vent.
COMBUSTIBLE MATERIAL WALL - A minimum clearance
of 1" to combustible materials must be maintained when using
Pub. No. 41-5016-12
CAUTION
ANCHORS
(4 req.)
VENT
PLATE
VENT
12" MINIMUM
TO OVERHANG
VENT
VENT
CAP
MAINTAIN 12" (18" FOR CANADA) MINIMUM
CLEARANCE ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE WHICHEVER IS GREATER
single wall stainless steel venting. See Figure 30.
Shield material to be a minimum of 24 gauge stainless or alumi-
nized sheet metal. Minimum dimensions are 12"x12". Shield
must be fastened to both inside and outside of wall. Use screws or
l
BAYAIR30AVENTA
(Sidewall)
For Canadian applications only, IPEX 196006, IPEX 081216, IPEX 081218,
and IPEX 081219 may be used for horizontal vent terminations.
;
SCREWS
(4 req.)
(1" ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE)
z
COUPLING
(PLASTIC
VENTING)
MORTAR SEAL
VENTING THROUGH NON-COMBUSTIBLE WALLS
Installation Instructions
COUPLING
PVC WALL
(PLASTIC
MOUNT FLANGE
STUD
VENTING)
(OPTIONAL)
6 IN. MIN.
(TO JOINT)
12" MINIMUM ABOVE
NORMALLY EXPECTED
SNOW ACCUMULATION
1" CLEARANCE
LEVEL
(AIR SPACE)
VENTING THROUGH COMBUSTIBLE WALLS
Pitch - 1/4 Inch Per Foot
CLEARANCE (0" ACCEPTABLE FOR PVC VENT PIPE)
PVC WALL
MOUNT FLANGE
(OPTIONAL)
6 IN. MIN.
(TO JOINT)
TERMINATION
12" MINIMUM ABOVE
CEMENT
NORMALLY EXPECTED
SNOW ACCUMULATION
INSIDE &
LEVEL
OUTSIDE
Pitch - 1/4 Inch Per Foot
APPROVED
TERMINATION
APPROVED
Page 17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents