Trane RuptureGuard CDHF Installation, Operation And Maintenance Manual page 11

Pressure relief system option
Table of Contents

Advertisement

Figure 10. Side view of RuptureGuard assembly
The surface of the
metal RuptureGuard
disk is extremely
fragile and the domed
portion of the disk
should never be
touched!
N N o o t t e e : : Positioning of RuptureGuard ™ pressure switch, pressure gauge, and excess flow valves is in the RuptureGuard ™
interspace. The excess flow valve should be positioned horizontally.
Figure 11. Correct RuptureGuard orientation
Pressure Switch
The drain in the bottom
of the casting should
always be directed
downward (±15°)!
N N o o t t e e : : Port orientation may vary.
CTV-SVX06J-EN
The drain in the bottom
of the casting should
always be directed
downward (±15°)!
Pressure Gauge
Excess flow valve needs
to be at or slightly above
the horizontal (never below)!
G G e e n n e e r r a a l l I I n n f f o o r r m m a a t t i i o o n n
11