Electrical Connections To Eac - Trane 4TEE3C01A1000A Installer's Manual

Variable speed – communicating air handlers
Table of Contents

Advertisement

!
HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC
POWER, INCLUDING REMOTE DISCONNECTS BEFORE
SERVICING. FOLLOW PROPER LOCKOUT/TAGOUT
PROCEDURES TO ENSURE THE POWER CAN NOT BE
INADVERTENTLY
DISCONNECT POWER BEFORE SERVICING COULD
RESULT IN DEATH OR SERIOUS INJURY.
PROCEDURE:
1)
On the communicating systems air handler, remove
the blower access panel.
2)
Remove the communicating control box cover.
3)
Locate the red jumper wire which is attached from
EAC to R on the Communicating Systems PCB.
Confirm it is connected. If there is not a jumper wire
installed, then one must be installed in this location
in order for the air cleaner to function properly.
Detach female spade terminal
from white EAC wire and
crimp to green wire
BEFORE
WHITE
GREEN
BK
R
O
G
Y1
Y2
D
B
W1
W2
W3
Indoor Unit
24V
Terminal
Strip Detail
18-GE14D1-5

ELECTRICAL CONNECTIONS TO EAC

WARNING
ENERGIZED.
FAILURE
AFTER
WHITE
GREEN
EAC
WHITE
GREEN
BK
R
O
G
Y1
Y2
D
B
W1
W2
W3
4)
Replace the Communicating control box cover.
5)
Locate the white wire coming from the Communi-
cating System Air Handler PCB labeled "EAC".
The wire will have a male spade terminal con-
nected to it and a female spade terminal inserted
into the male terminal. Remove the female spade
TO
terminal and crimp it to the green wire on the air
cleaner harness.
6)
Connect the green wire from the air cleaner
harness to the white wire on the Communicating
Systems Air Handler.
7)
Using the wire harness supplied with the air
cleaner, connect the Red and Blue wires from the
air cleaner harness to "R" and "B" on the Indoor
Unit 24V Terminal Strip respectively.
8)
Connect the Black wire from the air cleaner wire
harness to earth ground by attaching the wire to a
grounded screw that is connected to the metal air
handler chassis.
9)
Replace the blower access panel.
Control box panel cover
(Shown removed)
For use with AccuClean or
BLACK
CleanEffects Air Cleaner
GRD
Power / Control
Wiring Cable and Plug
GREEN
BLUE
RED
WHITE
BROWN /
Unused
Future Use
Installer's Guide
24V RED
jumper wire
from EAC to R
EAC
R
PCB Detail
Air Cleaner
Plug
17