Carrier 62E Installation, Start-Up And Service Instructions Manual
Carrier 62E Installation, Start-Up And Service Instructions Manual

Carrier 62E Installation, Start-Up And Service Instructions Manual

Energy recovery ventilators

Advertisement

Quick Links

CONTENTS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-21
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Step 6 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . . 16
• ELECTRICAL CONNECTIONS
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-32
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Internal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Rain Hoods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Energy Recovery Wheel . . . . . . . . . . . . . . . . . . . . . . . . . 22
Airflow Settings and Adjustments. . . . . . . . . . . . . . . 22
• UNITS WITH EZERV CONROL OPTION
Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
ComfortLink™ Interface Device . . . . . . . . . . . . . . . . . 27
Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-36
Wheel for Cleaning (62EB,E7 Units) . . . . . . . . . . . 32
for Cleaning (62ECC and 62E2C Units). . . . . . . . 33
Installing Wheel Segments. . . . . . . . . . . . . . . . . . . . . . . 33
(62EC-EU and 62E2-E6 Units) . . . . . . . . . . . . . . . . . 34
Belt Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
• ALTERNATE BELT REPLACEMENT METHODS
Removing the Service Door . . . . . . . . . . . . . . . . . . . . . 35
Replacing a Blower (All ERV Cabinets Except
62EB and 62E7 Units) . . . . . . . . . . . . . . . . . . . . . . . . . 35
• EXHAUST SIDE
• SUPPLY SIDE
Replacing a Blower (62EB and 62E7
Size Cabinets). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
• EXHAUST OR SUPPLY SIDE
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36,37
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Air Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53620007-01
Installation, Start-Up and
Service Instructions
Page
. . . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . . . . . . . . 6
. . . . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . 14
Printed in U.S.A.
Energy Recovery Ventilators
Wheel Drive Components . . . . . . . . . . . . . . . . . . . . . . . 37
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Replacing the Throwaway Filters . . . . . . . . . . . . . . . . 37
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . .CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance
functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service
personnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. These instructions describe how to install, start up, and
service 62E energy recovery ventilator (ERV) units.
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all discon-
nect locations to alert others not to restore power until work
is completed.
The 62E ERV units recover energy from building exhaust
air and pre-condition ventilation air. See Tables 1A-2B for unit
data. All 62EB-62EU units are configured for vertical dis-
charge (through the bottom). Vertical units may be installed on:
• a stand-alone roof curb
• a combination curb for direct coupled connection to a
rooftop unit
If horizontal supply and return is desired using a vertical
unit, the vertical unit may be installed on a horizontal supply/
return base.
NOTE: The horizontal supply/return base accessory includes a
roof curb. The horizontal supply/return base should NOT be
used with a stand-alone roof curb.
All 62E2-62E7 units are configured for horizontal discharge
(through the side). Horizontal units may be installed on a
stand-alone roof curb.
DIRECT COUPLED APPLICATIONS (Vertical) -
ERV unit can be installed directly coupled to a RTU (rooftop
unit). For vertical (through the roof) applications, the connec-
tion between the 62EB-62EU ERV unit and the RTU may be
Form 62E-C1SI
Pg 1
50 Hz
WARNING

GENERAL

8-10
Replaces: New
62E
Page
The

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 62E

  • Page 1: Table Of Contents

    The 62E ERV units recover energy from building exhaust air and pre-condition ventilation air. See Tables 1A-2B for unit data. All 62EB-62EU units are configured for vertical dis- charge (through the bottom).
  • Page 2 The combination roof curb is a single curb that supports both the ERV and the RTU and as UNIT 62E NOMINAL CAPACITY (L/s) CAPACITY RANGE (L/s)
  • Page 3 UNIT 62E NOMINAL CAPACITY (L/s) 3585 CAPACITY RANGE (L/s) 1650-4250 MAXIMUM SHIPPING 1232 WEIGHT (kg) MAXIMUM OPERATING 1118 WEIGHT (kg) UNIT DIMENSIONS (mm) Length (includes hoods) Width Height ROTARY ENERGY EXCHANGER Type Size (Diam x Depth) (mm) 1727 x 76...
  • Page 4 UNIT 62E NOMINAL CAPACITY (cfm) CAPACITY RANGE (cfm) MAXIMUM SHIPPING WEIGHT (lb) MAXIMUM OPERATING WEIGHT (lb) UNIT DIMENSIONS (in.) Length (includes hoods) Width Height ROTARY ENERGY EXCHANGER Type Size (Diam x Depth) (in.) Nominal Drive Motor Hp SUPPLY/EXHAUST FANS Type...
  • Page 5 UNIT 62E NOMINAL CAPACITY (cfm) 7,600 CAPACITY RANGE (cfm) 3,500-9,000 MAXIMUM SHIPPING 2,715 WEIGHT (lb) MAXIMUM OPERATING 2,465 WEIGHT (lb) UNIT DIMENSIONS (in.) Length (includes hoods) Width Height ROTARY ENERGY EXCHANGER Type Size (Diam x Depth) (in.) 68 x 3.0...
  • Page 6: Installation

    PREPARE ROOF CURB LOCATION — Cut a hole in the roof for duct openings. Your local Carrier sales representative can provide dimensional drawing for the combination curb. See this drawing for duct opening dimensions. Frame the open- ing to provide adequate structural support.
  • Page 7: Step 4 - Install Horizontal Base And Transition

    (62EB-EU and 62E2-E7 Units) — zontal transition accessory is used to connect the ERV to the horizontal return of a Carrier rooftop unit. To provide horizon- tal exhaust and ventilation air connections on 62EB-EU units, the horizontal base accessory must also be installed. The acces- sory is not needed on 62E2-E7 units.
  • Page 8 Fork Pockets (Remove Before Installing on Curb) LEFT SIDE 62E UNIT TYPE 31.138 36.000 36.000 38.625 18.000 36.000 44.425 18.000 45.000 54.625 20.000 55.000 67.045 20.000 65.000 77.625 27.000 75.000 62E UNIT TYPE 1128 1143 1387 1397 1703 1651 1972...
  • Page 9 Fork Pockets (Remove Before Installing on Curb) LEFT SIDE 62E UNIT TYPE 82.750 30.000 89.750 30.000 95.750 30.000 100.750 32.000 108.750 32.000 112.750 32.000 119.750 32.000 125.625 32.000 62E UNIT TYPE 2102 2280 2432 2559 2762 2864 3042 3191 NOTES: 1.
  • Page 10 A62-247ef GASKETING ROOF CURB NAIL* RIGID INSULATION* FLASHING* CANT STRIP* ROOF FELT* ROOF DECK* ROOF* *Field provided. Fig. 4 — Roofing Materials — Recommendation a62-376.eps NOTE: All dimensions shown in inches. Fig. 5 — Typical Installation with Drop-in Damper Box A62-246ef SIDE Fig.
  • Page 11 "A" I.D. "A" I.D. 14.000 NOTES: 1. All dimensions shown in inches. 2. Nailer sits even with top of curb. Do not cover any existing holes with nailer. DIMENSION DIMENSION UNIT A (in.) B (in.) TYPE 27.221 24.721 34.721 32.221 40.521 38.021 50.721...
  • Page 12 a62-378 25.00 NOTE: All dimensions shown in inches. Fig. 8 — Typical 62EB-EU Unit Installation with Horizontal Base and Horizontal Transition RETURN AIR OPENING ENERGY RECOVERY UNIT HVAC UNIT HORIZONTAL TRANSITION a62-443 SUPPLY OPENING Fig. 9 — Typical 62E2-E7 Unit Installation...
  • Page 13 "D" DUCT O.D. "A" CLEARANCE "E" 36.000 CLEARANCE "F" "G" 62E UNIT TYPE 36.000 36.000 18.000 36.000 18.000 40.000 18.000 50.000 24.000 64.000 18.000 75.000 62E UNIT TYPE 1016 1270 1626 1905 NOTES: 1. Clearance above cabinet is 24 in. (610 mm).
  • Page 14: Step 5 - Install Standard Roof Curb

    ASSEMBLE THE ROOF CURB — Connect the curb side and the curb end. Insert the tabs on the curb end into the slots on the curb sides. See Fig 6. Press firmly until the pieces lock in to place. It may be necessary to exert additional force to the top of the curb to lock the pieces in place.
  • Page 15 "C" "B" I.D. SECTION A-A "A" DIMENSIONS (in.) 62E UNIT TYPE 28.286 10.143 31.397 36.927 33.816 35.882 13.941 38.993 40.446 37.335 41.682 16.841 44.793 40.306 37.195 51.882 21.941 54.993 48.826 45.715 64.302 28.151 67.413 54.286 51.175 74.882 33.441 77.993 60.236 57.125 NOTE: Dimensions are in inches.
  • Page 16: Step 6 - Rig And Place Unit

    Avoid twisting or uneven lifting of the unit. Never lift the unit by the hoods or any means other than the provided lifting holes or eyes. FORK POCKETS (REMOVE BEFORE INSTALLING ON CURB) 62E UNIT TYPE 27.221 34.721 40.521 50.721...
  • Page 17: Step 7 - Make Electrical Connections

    HVAC unit and the ERV controls to ensure proper operation of the ERV’s supply/exhaust fan and energy recovery wheel motors. The 62E has discrete inputs for this purpose and EYE HOOK damper end switches or relays may be used to coordinate the economizer and power exhaust operation with the ERV.
  • Page 18 Table 4 — Supply and Exhaust Fans Electrical Data OPTION CHASSIS D,E,3,4 E,H,K, 4,5,6 H,K,L, M,N,P, L,M,N, R,S, R,S, S,T,U H,K,L LEGEND FLA — Full Load Amps Qty — Quantity — Watts UNIT V-Ph V-Ph 115-1 115-1 230-1 230-1 230-3 230-1 460-3 200-1...
  • Page 19 3.64 2900 2.92 2700 6.79 2700 3.39 2700 3.39 2700 2.71 2700 6.79 2700 3.39 2700 3.39 2700 2.71 62E CHASSIS B,C,2,7 B,C,D,E,2,3,4,7 B,C,D,E,2,3,4,7 B,C,D,E,2,3,4,7 B,C,D,E,2,3,4,7 B,C,2,7 B,C,D,E,H,2,3,4,5,7 B,C,D,E,H,2,3,4,5,7 B,C,D,E,H,2,3,4,5,7 B,C,D,E,H,2,3,4,5,7 D,E,H,3,4,5 D,E,H,3,4,5 D,E,H,3,4,5 D,E,H,3,4,5 E,H,K,L,4,5,6 E,H,K,L,4,5,6 E,H,K,L,4,5,6 E,H,K,L,4,5,6 H,K,L,M,N,5,6...
  • Page 20 400-3 460-3 575-3 230-3 400-3 460-3 575-3 230-3 400-3 460-3 575-3 230-3 400-3 460-3 575-3 230-3 400-3 460-3 575-3 62E CHASSIS H,K,L,M,N,P,R,S,5,6 H,K,L,M,N,P,R,S,5,6 H,K,L,M,N,P,R,S,5,6 H,K,L,M,N,P,R,S,5,6 K,L,M,N,P,R,S,T,U,6 K,L,M,N,P,R,S,T,U,6 K,L,M,N,P,R,S,T,U,6 K,L,M,N,P,R,S,T,U,6 L,M,N,P,R,S,T,U L,M,N,P,R,S,T,U L,M,N,P,R,S,T,U L,M,N,P,R,S,T,U M,N,P,R,S,T,U M,N,P,R,S,T,U M,N,P,R,S,T,U M,N,P,R,S,T,U N,P,R,S,T,U N,P,R,S,T,U N,P,R,S,T,U...
  • Page 21 ERV OPTION BOARD #2 ERV OPTION BOARD #1 Fig. 14 — Typical Wiring Schematic...
  • Page 22: Start-Up

    START-UP Use the following information to check unit PRIOR to start-up. CAUTION Before turning the disconnect switch on, verify that the voltage being provided to the ERV unit matches the volt- age shown on the ERV nameplate. Failure to do so could result in equipment damage.
  • Page 23 Table 6 — Airflow vs. Pressure Drop Across ERV Wheel 62E UNIT BA,7A BC,7C CC,2C CD,2D CG,2G DD,3D DG,3G EB,4B ED,4D EF,4F 944 1038 1133 1227 1322 1416 1510 1605 1699 EG,4G 944 1038 1133 1227 1322 1416 1510 1605 1699...
  • Page 24 Table 6 — Airflow vs. Pressure Drop Across ERV Wheel (cont) UNIT 1652 1888 2124 2360 2360 2832 3068 3304 2124 2360 2596 2832 2832 3304 3776 4248 2596 2832 3068 3304 3540 4012 4484 4956 2832 3304 3776 4012 3776 4248 4720...
  • Page 25: Operating Sequence

    The sequence of operation is shown in Fig. 24. LOW TEMPERATURE LOCKOUT — The optional low temperature lockout function locks out the 62E ERV if the out- level. See Fig. 22. door-air temperature entering the wheel is below the set point.
  • Page 26 HVAC Supply Fan On or ERV Timer Option Active or Stand Alone Short Pins 31 to 30 and 29 to 28 TRUE TRUE Low Temp Lock Out FALSE Option 51 Lockout Activated TRUE FALSE CO2 Level Not High Enough in TRUE Space FALSE...
  • Page 27: Comfortlink™ Interface Device

    ComfortLink™ Interface Device — the device is to provide factory-installed “Plug and Play” con- trol interface between the 62E and a Carrier rooftop unit Com- fortLink control system. The interface allows for optimal sys- tem operation by sharing unit data and properly coordinating energy recovery, economizer, and power exhaust operation.
  • Page 28 BT485 TERMINATOR BACNET CONNECTION (BAS PORT) Tx1 LED Rx1 LED Tx2 LED Rx2 LED EIA-485 JUMPERS Fig. 25 — UPC Open Controller Fig. 26 — Network Wiring POWER LED BACNET BAUD RATE DIP SWITCHES ADDRESS ROTARY SWITCHES RUN LED ERROR LED...
  • Page 29 SPECIFICATION Cable Conductor Insulation Color Code Twist Lay Shielding Jacket DC Resistance Capacitance Characteristic Impedance Weight UL Temperature Rating Voltage Listing LEGEND — American Wire Gage CL2P — Class 2 Plenum Cable — Direct Current — Fluorinated Ethylene Polymer — National Electrical Code O.D.
  • Page 30 EIA-485 and 2W. The example in Fig. 29 shows the BAS Port DIP Switches set for 76.8k (Carrier default) and MS/TP. Set the BAS Port DIP Switches DS2 and DS1 for the appro- priate communications speed of the MS/TP network (9600, 19.2k, 38.4k, or 76.8k bps).
  • Page 31 BACNET OBJECT ID AV:1 AV:2 DCV_CO2_INSIDE AV:3 AV:4 AV:5 EXHAUST_AIR_CFM AV:6 AV:7 AV:8 OUTSIDE_AIR_CFM AV:9 AV:10 REMOTE_AIRFLOW_CONFIGURATION_MODE AV:11 REMOTE_BP_SENSOR AV:12 REMOTE_BP_SETPOINT AV:13 REMOTE_EXHAUST_OFFSET_SETPOINT AV:14 REMOTE_MAX_CFM_SETPOINT AV:15 REMOTE_MAX_DCV_VALUE_SETPOINT AV:16 REMOTE_MIN_CFM_SETPOINT AV:17 REMOTE_MIN_DCV_VALUE_SETPOINT AV:18 REMOTE_SENSOR_DCV_VALUE AV:19 AV:20 UPC_SOFTWARE_VERSION_STAT AV:21 UPC_SOFTWARE_VERSION AV:22 AV:23 AV:24 REMOTE_EX_FILTER_BP_SETPOINT AV:25...
  • Page 32: Service

    SENSOR ENABLE (BV:12) is set to 0, then the ERV will use the DCV CO2 INSIDE (AV:2) parameter. Any value can be written into this parameter. The ERV will look at this parameter along with parameters: REMOTE MIN DCV VALUE SETPOINT (AV:17), RE- MOTE MAX DCV VALUE SETPOINT (AV:15), REMOTE MIN CFM SETPOINT (AV:16), and REMOTE MAX CFM SETPOINT (AV:14) to determine the settings for the ERV.
  • Page 33: Removing And Installing Non-Segmented Wheel

    engages the notch at the end of the shaft when reinstalling the wheel. 4. Pull the wheel straight off the shaft. Handle wheel with care to prevent distorting of the wheel. Removing Installing Wheel Cleaning (62ECC and 62E2C Non-segmented energy transfer wheels include Units) —...
  • Page 34: Wheel Drive Motor And Pulley Replacement

    Fig. 33 — Using a Stop on the Wheel NOTE: The 62EBA, 62EBC, 62ECC, 62E7A, 62E7C, and 62E2C units contain non-segmented wheels which must be completely removed to be cleaned. 1. Begin by positioning one segment opening at the top of the cassette.
  • Page 35: Removing The Service Door

    Pry the top panel up from its gasket seat, being careful not to bend the lid. Re- move the cover from the blower motor and note the location of WHEEL MODEL 62E UNIT SIZE ERV WHEEL NUMBER ERC-1904 ERC-1906...
  • Page 36: Size Cabinets)

    Bearing Access Plate Retaining Screws Set Screw Drift Hole Locating Pin Belt Fig. 38 — Belt Replacement (Diameter Seals Removed) Replacing a Blower (62EB and 62E7 Units) EXHAUST OR SUPPLY SIDE — Turn off the power to the unit. Remove all of the screws from the top panel. Pry the top panel up from its gasket seat, being careful not to bend the lid.
  • Page 37: Wheel Drive Components

    as a feeler gage, position paper between the wheel surface and diameter seals. Adjust seals towards wheel surface until a slight friction on the feeler gage (paper) is detected when gage is moved along the length of the spoke. Retighten adjusting screws and recheck clearance with “feeler”...
  • Page 38: Troubleshooting

    The wheel belt is off or broken The air seals on the wheel are too tight Copyright 2010 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53620007-01 Printed in U.S.A.
  • Page 40: Start-Up Checklist

    Field-Installed Accessories ERV Remote Mount Timer (Field Installed) ERV Remote Control Readout (Field Installed) Copyright 2010 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53620007-01 Printed in U.S.A.

Table of Contents