Max. Alternator Current Low.
illuminates red, the alarm horn sounds, and the unit
shuts down when Alternator Protection Configuration in
the personality profile is not correct. If the settings are
correct for the application, the controller may need a
new or updated personality profile. Consult your local
authorized distributor.
Oil Pressure Open Circuit. The fault lamp illuminates
red, the alarm horn sounds, and the unit shuts down
when the engine oil pressure sender circuit is open for
more than 5 seconds.
Overcrank. The fault lamp illuminates red, the alarm
horn sounds, and cranking stops when the unit does not
start within the defined cranking period. See Section
2.6 for cyclic crank specifications.
Run Relay Coil Overload. The fault lamp illuminates
red, the alarm horn sounds, and the unit shuts down
when the current draw on the 70 wire from the controller
has exceeded 40 amps or has exceeded 10 amps for at
least 10 ms.
56
Section 2 Operation
The fault lamp
Starter Relay Coil Overload.
illuminates red, the alarm horn sounds, and the unit
shuts down when the current draw on the 71 wire from
the controller has exceeded 40 amps or has exceeded
10 amps for at least 10 ms.
Trip to Shutdown Delay The fault lamp illuminates red,
the alarm horn sounds, and the unit shuts down when
the generator is stopped if the circuit breaker has tripped
for a Protective Relay function, and the trip to shutdown
time delay has expired. This delay allows mitigation of
problem conditions without engine shutdown. If the
delay expires, it is presumed no successful action was
taken in the allotted time.
The fault lamp
TP-7126 5/20