Kidde Gemini II System
TB1000
+
BATTERY
-
2 EACH 12
VDC
-
BATTERIES
2 EACH P/N 06-115915-047 :
2 EACH P/N 06-115915-046 :
2 EACH P/N 89-100052-001 :
TB7
MODULE 1
(MCP)
RS485 CHANNEL 1
RS485 CHANNEL 2
RS485 CHANNEL 1
A1
A1
A1
B1
A2
B2
B1
A2
B2
DATA PAIR 1
DATA PAIR 2
NOTES:
1.
TWO INDEPENDENT DATA PAIRS MUST BE USED FOR THE RS-485 NETWORK. BOTH PAIRS MUST BE ROUTED SO TO ALWAYS BE IN SEPARATE CONDUITS.
2.
THE MAXIMUM LENGTH OF EACH RS-485 LOOP MUST NEVER EXCEED 4000 FEET (1219 METERS).
3.
USE MINIMUM 24 AWG TWISTED PAIR WITH SHUNT CAPACITANCE OF 16pF PER FOOT AND 100 OHM CHARACTERISTIC IMPEDANCE. FOR INSTALLATIONS UNDER ADVERSE CONDITIONS (FOR EXAMPLE
WHERE HIGH ELECTRICAL NOISE IS EXPECTED), THE USE OF TWISTED SHIELDED PAIRS IS RECOMMENDED.
4.
WHEN USING TWISTED SHIELDED PAIRS, FOR EACH PAIR, THE SHIELD MUST ONLY BE TERMINATED AT THE GROUND LUG ON THE LEFT SIDE OF TB 7 ON THE MCP. FOR INTERMEDIATE UNITS, THE SHIELD
FROM THE INCOMING PAIR MUST BE CONNECTED TO THE SHIELD OF THE OUTGOING PAIR SO AS TO BE CONTINUOUS THROUGHOUT THAT LOOP. THE SHIELD ON THE LAST UNIT MUST BE CUT SHORT AND
LEFT FLOATING.
5.
MODULE 1 (ALWAYS THE MCP) AND MODULE N (LAST UNIT) MUST HAVE EOL LINKS FITTED (AS SHOWN BELOW) WHILE ALL OTHER MODULES MUST NOT.
W-FLOW
W104
1
2
3
MCP MODULE 1
SHORT W104
PINS 5 TO 6 & 7 TO 8
Figure E-9. Dual Channel Class A, Style 7 RS-485 Communications Highway
06-235975-001
+
-
12 AH, 24 VDC
17 AH, 24 VDC
33 AH, 24 VDC
Figure E-8. Detail of Battery Connections
MODULE
2 TO M-1
RS485 CHANNEL 2
RS485 CHANNEL 1
A1
A1
B1
A2
B2
B1
A2
B2
B1
W104
4
5
6
7
8
1
RHU MODULE N (LAST UNIT)
firealarmresources.com
TB1000
+
BATTERY
-
4 EACH 12
VDC
+
BATTERIES
4 EACH P/N 06-115915-047 : 24 AH, 24 VDC
4 EACH P/N 06-115915-046 :
4 EACH P/N 89-100052-001 :
MODULE
M
RS485 CHANNEL 2
RS485 CHANNEL 1
A1
A1
A2
B2
B1
A2
B2
B1
W-FLOW
2
3
4
5
6
7
8
SHORT W104
PINS 5 TO 6 & 7 TO 8
E-8
-
+
-
-
+
-
34 AH, 24 VDC
66 AH, 24 VDC
MODULE
M+1 TO N-1
RS485 CHANNEL 2
RS485 CHANNEL 1
A1
A1
A2
B2
B1
A2
B2
B1
A2
W1
1
2
3
4
RDU MODULE N (LAST UNIT)
SHORT W1
PINS 1 TO 2 & 3 TO 4
+
+
MODULE
N
RS485 CHANNEL 2
A1
B2
B1
A2
B2