Hitachi CONVENTION 14 Instruction Manual page 265

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Table of Contents

Advertisement

B − 22
B 22
The following table lists holding registers for the "D" Group Monitor Functions.
Func.
Code
D001
Output frequency
monitor
D002
Output current
monitor *1
D003
Rotation direction
monitor
D004
Process Variable (PV),
(high)
PID feedback monitor
D004
(low)
D005
Intelligent input
terminal status
D006
Intelligent output
terminal status
D007
Scaled output
(high)
frequency monitor
D007
(low)
D013
Output voltage
monitor
D016
Cumulative operation
(high)
RUN time monitor
D016
(low)
D017
Cumulative power-on
(high)
time monitor
D017
(low)
D018
Fin temperature
monitor
D080
Trip counter
D102
DC voltage monitor
D104
Electronic thermal
monitor
Note 1:
List of Holding Registers
Name
R/W
R
Real-time display of output
frequency to motor, from 0.0 to
400.0 Hz
R
Filtered display of output
current to motor (100 ms
internal filter time constant),
range is 0 to 200% of inverter
rated current
R
Three different indications:
00...Stop
01...Forward
02...Reverse
R
Displays the scaled PID process
variable (feedback) value (A075
is scale factor), range is 0.00 to
R
9999.00
R
Displays the state of the
intelligent input terminals [x],
Bit 0 = [1] to Bit 4 = [5]
R
Displays the state of the
intelligent output terminals [x],
Bit 0 = [11], Bit 1 = (Don't Care),
Bit 2 = [AL]
R
Displays the output frequency
scaled by the constant in B086.
Decimal point indicates range:
R
0.00 to 39960.00
R
Voltage of output to motor, range
is 0.00 to 200.00%
R
Displays total time the inverter
has been in RUN mode in hours.
R
Range is 0 to 999999
R
Displays total time the inverter
has been in RUN mode in hours.
Range is 0 to 999999
R
R
Display the Fin temperature in
0.0~200.0 C
R
Number of trip events, range is 0
to 65535
R
Voltage of DC bus inside
inverter,Range is 0.0 to 999.9
R
Accumulated value of electronic
thermal detection, range is from
0.0 to 100.0
Assume that the inverter current rating is 1000 (for D002).
Description
Network Data
Reg.
Range
Res.
1002h
0 to 4000
0.1 Hz
1003h
0 to 2000
0.1%
1004h
0,1,2
1005h
0 to
0.00%
999900
times
const.
1006h
1007h
0 to 63
1008h
0 to 7
1009h
0 to
0.01 Hz
3996000
times
const.
100Ah
100Ch
0 to
0.01%
20000
100Eh
0 to
1 hour
999999
100Fh
1010h
0 to
1 hour
999999
1011h
116Ah
0 to 2000
0.1 C
0011h 0 to 65535
1 trip
event
116Ch
0 to 9999
0.1 V
116Dh
0 to 1000
0.1 %

Advertisement