2.6 Electrical Connections

WARNING
Hazardous voltage.
Backfeed to the utility system can
cause property damage, severe
injury, or death.
If the generator set is used for
standby power, install an automatic
transfer switch to prevent inadvertent
interconnection
normal sources of supply.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards.
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.
Electrical backfeed to the utility. Hazardous backfeed
voltage can cause severe injury or death. Install a transfer
switch in standby power installations to prevent the connection
of standby and other sources of power. Electrical backfeed
into a utility electrical system can cause severe injury or death
to utility personnel working on power lines.
1
1. Factory-connected to generator
2. Secure to building wall using clamp (provided)
3. Field connections to ATS
Figure 2-13 Wiring Kit
20
Section 2 Installation
of
standby
and
Electrically ground the
set
NOTICE
Canadian installations only. For standby service connect
the output of the generator set to a suitably rated transfer
switch in accordance with Canadian Electrical Code, Part 1.
Have an authorized distributor/dealer or a licensed
electrician make the following electrical connections.
Verify that the electrical installation complies with the
National Electrical Code (NEC) and all applicable local
codes. Ground generator set according to applicable
codes.
2.6.1

Generator Set Connections

The factory-installed wiring kit eliminates the need to
make field connections inside the generator set junction
box. The wiring kit includes a wiring harness and an AC
outlet mounted inside the generator set enclosure for
the battery charger and accessories. See Figure 2-13.
The wiring harness includes the engine start leads,
power leads to the AC outlet, and the emergency power
leads. The leads exit the generator set in 1 1/4 inch
conduit with liquid-tight connections. Cut a 2-inch hole
through the building wall to bring the PVC end of the
conduit into the building. Secure the PVC assembly to
the wall using the clamp provided. Seal the gap around
the conduit with caulk. Use duct seal inside the conduit if
desired.
2
3
GM46984