5. PI/O Module
SAO06 module internal circuit, and the extent of fault diagnostics
 Diagnostic functions
Output current read-back diagnostics
ROM/RAM check; WDT supervision; and power supply supervision
I/O bus transmission diagnostics
Duplex switching status diagnostics
*1: Part of the duplex switching circuit is not subject to diagnostics. At the time of
regular repair, it is possible to check the presence or absence of errors by
conducting duplex switching tests.
*2: In standby operation, the output diode open failure may not be detected; in online
operation, the short-circuit failure may not be detected. At the time of regular
repair, it is possible to check the presence or absence of errors by conducting
duplex switching tests.
*3: The panel SW and the status display are not included in the diagnostics. At the time
of regular repair, it is possible to check the presence or absence of any panel SW
failure as well as the illumination status of panel LEDs by conducting the power
ON/OFF tests.
*4: One-off errors may not be detected depending on diagnostic cycle timing, etc.
126
AO1(+)
AO1( - )
AO8(+)
AO8( - )
AO1(+)
AO1( - )
AO8(+)
AO8( - )
UTBA6
Signal
D/A conver-
isolation
sion circuit
circuit
with analog
lead-back
Internal
power supply
DC/DC
Isolation analog circuit
converter
power supply
(Module connector)
24 V
SAO06 (PRM)
Signal
D/A conver-
isolation
sion circuit
circuit
with analog
lead-back
Internal
power supply
DC/DC
Isolation analog circuit
converter
power supply
(Module connector)
24 V
SAO06 (SCD)
1)
Status
indicator/
switch
2)
Internal
CPU circuit
3)
RS-485
RS-485
trans-
trans-
ceiver
ceiver
4)
Dualized switching signal
1)
Status
indicator/
2)
switch
Internal
CPU circuit
3)
RS-485
RS-485
trans-
trans-
ceiver
ceiver
4)
Dualized switching signal

Advertisement

Table of Contents
loading

This manual is also suitable for:

V 1000V 2000V 3000

Table of Contents