Retry Mode; Aquazone Deluxe D Control Led Indicators - Carrier AQUAZONE 50PSW036-360 Installation And Service Instructions Manual

Water-to-water water source heat pump with puron refrigerant (r-410a)
Hide thumbs Also See for AQUAZONE 50PSW036-360:
Table of Contents

Advertisement

Upon entering Test mode, the status LED (light-emitting di-
ode) will flash a code representing the last fault. For diagnostic
ease at the thermostat, the alarm will also cycle during Test
mode. The alarm relay will cycle on and off similar to the sta-
tus LED to indicate a code representing the last fault, at the
thermostat. Test mode can be exited by shorting the test termi-
nals for 3 seconds. See Tables 10-12.
NOTE: Deluxe D control has a flashing code and alarm relay
cycling code that will both have the same numerical label.
For example, flashing code 1 will have an alarm relay cycling
code 1. Code 1 indicates the control has not faulted since the
last power off to power on sequence.
In Retry mode, the status LED will start to
Retry Mode —
flash slowly to signal that the control is trying to recover from
an input fault. The control will stage off the outputs and try to
again satisfy the thermostat used at terminal Y. Once the ther-
mostat input calls are satisfied, the control will continue normal
operation.
NOTE: If 3 consecutive faults occur without satisfying the
thermostat input call to terminal Y, the control will go into
lockout mode. The last fault causing the lockout is stored in
memory and can be viewed by entering Test mode.
Table 10 — Complete C Control Current LED
Status and Alarm Relay Operations
DESCRIPTION OF
LED STATUS
OPERATION
Normal Mode
On
Normal Mode with PM Warning
Off
Control is non-functional
Fault Retry
Slow Flash
Over/Under Voltage Shutdown
Fast Flash
Lockout
Flashing Code 1
Test Mode — No fault in memory
Flashing Code 2 Test Mode — HP Fault in memory
Flashing Code 3 Test Mode — LP Fault in memory
Flashing Code 4 Test Mode — FP1 Fault in memory
Flashing Code 5 Test Mode — FP2 Fault in memory
Test Mode — Over/Under shut-
Flashing Code 7
down in memory
Flashing Code 8
Test Mode — PM in memory
Test Mode — FP1/FP2 swapped
Flashing Code 9
fault in memory
LEGEND
FP
— Freeze Protection
HP
— High Pressure
LED — Light-Emitting Diode
LP
— Low Pressure
PM
— Performance Monitor
NOTES:
1. Slow flash is 1 flash every 2 seconds.
2. Fast flash is 2 flashes every 1 second.
3. EXAMPLE: "Flashing Code 2" is represented by 2 fast flashes followed
by a 10-second pause. This sequence will repeat continually until the
fault is cleared.
Aquazone™ Deluxe D Control LED Indica-
tors —
STATUS LED — Status LED indicates the current status or
mode of the Deluxe D control. The Status LED light is green.
TEST LED — Test LED will be activated any time the De-
luxe D control is in Test mode. The Test LED light is yellow.
FAULT LED — Fault LED light is red. The fault LED will
always flash a code representing the last fault in memory. If
there is no fault in memory, the fault LED will flash code 1 on
the display and appear as 1 fast flash alternating with a
10-second pause. See Table 12.
Table 11 — Complete C Control LED Code and
ALARM RELAY
Open
Cycle
(Closed 5 sec.,
Open 25 sec.)
(Autoreset)
Open
Open
Open
(Closed after
15 minutes)
Closed
Cycling Code 1
Cycling Code 2
FP
Cycling Code 3
HP
LP
Cycling Code 4
Cycling Code 5
Cycling Code 7
Cycling Code 8
Cycling Code 9
17
There are 3 LED indicators on the Deluxe D control:
Fault Descriptions
LED
FAULT
CODE
1
No fault in memory
2
High-Pressure Switch
3
Low-Pressure Switch
4
Freeze Protection
(Source) Coax — FP1
5
Freeze Protection (Load)
Coil — FP2
7
Over/Under Voltage
Shutdown
8
PM Warning
9
FPI and FP2
Thermistors are
swapped
LEGEND
— Freeze Protection
— High Pressure
— Low Pressure
DESCRIPTION
There has been no fault since
the last power-down to power-up
sequence
HP Open Instantly
LP open for 30 continuous
seconds before or during a
call (bypassed for first
60 seconds)
FP1 below Temp limit for
30 continuous seconds
(bypassed for first 60 seconds of
operation)
FP2 below Temp limit for
30 continuous seconds
(bypassed for first 60 seconds of
operation)
"R" power supply is <19 vac
or >30 vac
Performance Monitor
Warning has occurred.
FP1 temperature is higher than
FP2 in heating/test mode, or FP2
temperature is higher than FP1
in cooling/test mode.