Carrier AIR COOLED SPLIT SYSTEM 38AQS008 Installation And Service Instructions Manual page 7

Air-cooled split system heat pump 50/60 hz
Hide thumbs Also See for AIR COOLED SPLIT SYSTEM 38AQS008:
Table of Contents

Advertisement

UNIT
NOMINAL VOLTAGE
38AQS
(V-Ph-Hz)
208/230-3-60
460-3-60
008
220-3-50
400-3-50
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
NEC
— National Electrical Code (U.S.A.)
OFM
— Outdoor Fan Motor
RLA
— Rated Load Amps
(60 Hz Only)
(60 Hz Only)
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percent voltage imbalance.
max voltage deviation from average voltage
= 100 x
average voltage
Table 4 — Electrical Data
VOLTAGE RANGE
COMPRESSOR
Min
Max
RLA
187
254
31.5
414
508
15.7
198
242
39.7
360
440
19.9
OFM
POWER SUPPLY
MAX FUSE OR
LRA
FLA
MCA
HACR BRKR AMPS
160
3.1
42.5
80
1.4
21.0
198
3.1
52.7
99
1.4
26.3
Example: Supply voltage is 460-3-60.
(AB) 457
452 = 5 v
(BC) 464
457 = 7 v
(AC) 457
455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance
% Voltage Imbalance = 100
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more
than 2%, contact your local electric utility company
immediately.
7
MINIMUM DISCONNECT
FLA
50
45
25
25
70
55
35
30
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
=
457
7
457
= 1.53%
LRA
177
89
205
106

Hide quick links: