6.2 Accessory and Prime Power
Terminal Strip Connections
(DEC 3+)
The 16-light controller circuit board has terminal strips
for use in connecting a controller connection kit. Do not
connect accessories directly to the controller terminal
strip(s).
Connect accessories to either a controller
connection kit or dry contact kit. Connect the dry contact
kit(s) to the controller connection kit. Connect alarms,
battery
chargers,
remote
accessories to the dry contact kit relay(s).
The 16-light controller has two terminal strips, TB1 and
TB2, on the controller circuit board, and prime power
choices are made on TB2.
controller configurations.
Figure 6-37 for controller terminal strip identification.
See Figure 6-38, Figure 6-39, and Figure 6-40 for
accessory connection wiring diagrams.
Lower the controller circuit board panel until it is lying flat
when connecting the dry contact kits to the controller
TB1 terminal strip.
Route dry contact relay leads
through the controller grommet and guide loops to the
circuit board terminal strip. Place the controller circuit
board panel flat to ensure adequate slack in the dry
contact relay leads.
accessory connections refer to the accessory wiring
diagrams in the Wiring Diagram Manual and the
instruction sheet accompanying the kit.
Note: Not all terminals are used for all generator sets
(see appropriate wiring diagrams for specific
generator set models).
Note: To use the prime power mode, use jumpers to
connect TB2-1P to TB2-2P, TB2-3P to TB2-4P,
and TB2-3 to TB2-4. To deactivate the prime
power mode, remove these jumpers.
66
Section 6 Accessories
switches,
and
See Figure 6-35 for
See Figure 6-36 and
For specific information on
1
other
1. TB1 (TB1A) terminal strip
2. TB2 terminal strip
3. TB3 (TB1B) terminal strip
Figure 6-35 TB1 and TB2 Terminal Strips on the
Terminal
Purpose
1P
Prime power operation.
2P
Prime power operation.
Remote start ground. Connect transfer switch or
3
remote start switch to TB2--3 and TB2--4.
3P
Prime power operation.
Remote start. Connect transfer switch or remote
4
start switch to TB2--3 and TB2--4.
4P
Prime power operation.
Crank mode selection (open: cyclic crank, ground:
continuous crank). Connect TB2--9 to TB2--9A for
9
continuous cranking; leave TB2--9 open cyclic
cranking; see starting instructions in Section 2,
Operation.
9A
Crank mode ground.
Figure 6-36 16-Light Controller TB2 Terminal Strip
3
R41
LED4
P2
P1
16-Light Controller
2
A-336415-A
TP-6161
1/12