For the air conditioner, connect a power wire with the
following specifications.
Model RAV-
GM110, GM140
220-240 V~, 50 Hz
Power supply
220 V~, 60 Hz
Maximum running current
22.8 A
Installation fuse rating
25 A (all types can be used)
H07 RN-F or 60245 IEC 66
Power supply wire
(4 mm
2
or more)
H07 RN-F or 60245 IEC 66
System interconnection
wires
2
(1.5 mm
or more)
How to wire
1. Remove the mounting screws (2 pieces), open the
electrical control box cover.
2. Connect the power supply wires and system
interconnection wires to the terminal block of the
electrical control box.
3. Tighten the screws of the terminal block, connect the
wires matching the terminal numbers (Do not apply
tension to the connecting section of the terminal
block.)
4. Close the electrical control box cover, attach the
mounting screws.
When connecting the system interconnection wire to
the outdoor unit terminal, prevent water from coming
into the outdoor unit.
Insulate the unsheathed cords (conductors) with
electrical insulation tape. Process them so that they
do not touch any electrical or metal parts.
For system interconnection wires, do not use a wire
joined to another on the way.
Use wires long enough to cover the entire length.
To Indoor unit
Power supply
terminal block
terminal block
1
2
3
L
Earth
Earth
screw
screw
Pipe valve
fixing plate
System
Power supply wire
interconnection
wire
33-EN
Stripping length power cord and system
interconnection wire
10
1 2 3
10
50
50
30
(mm)
Earth wire
Earth wire
System
interconnection
wire
Wiring diagram
* For details on the remote controller wiring /
installation, refer to the Installation Manual enclosed
with the remote controller.

Single system

Remote controller
Remote controller wiring
A B
Indoor side
1
2
3
System interconnection
wires
1
2
3
Outdoor side
L
N
Power supply
Simultaneous twin system
Remote controller
Remote controller
wiring
A B
Indoor side
1
2
3
System
interconnection wires
N
1
2
3
Outdoor side
L
N
Power supply
* Use 2-core shield wire (MVVS 0.5 to 2.0 mm² or
more) for the remote controller wiring in the
simultaneous twin system to prevent noise
problems. Be sure to connect both ends of the shield
wire to earth leads.
* Connect earth wires for each indoor unit in the
simultaneous twin system.
– 17 –
8

Earthing

L N
10
WARNING
10
Be sure to connect the earth wire. (grounding work)
40
Incomplete grounding may cause an electric shock.
Connect the earth wire properly following applicable technical standards.
Connecting the earth wire is essential to preventing electric shock and to reducing noise and electrical charges on
Power supply
the outdoor unit surface due to the high-frequency wave generated by the frequency converter (inverter) in the
wire
outdoor unit.
If you touch the charged outdoor unit without an earth wire, you may experience an electric shock.
9

Finishing

After the refrigerant pipe, inter-unit wires, and drain pipe have been connected, cover them with finishing tape and
clamp them to the wall with off-the-shelf support brackets or their equivalent.
Keep the power wires and system interconnection wires off the valve on the gas side or pipes that have no heat
insulator.
10

Test run

• Turn on the leakage breaker at least 12 hours before starting a test run to protect the compressor during
startup.
To protect the compressor, power is supplied from the 220-240 VAC input to the unit to preheat the compressor.
• Check the following before starting a test run:
• That all pipes are connected securely without leaks.
• That the valve is open.
Remote
If the compressor is operated with the valve closed, the outdoor unit will become overpressurized, which may
controller
inter-unit
damage the compressor or other components.
wiring
If there is a leak at a connection, air can be sucked in and the internal pressure further increases, which may
cause a burst or injury.
• Operate the air conditioner in the correct procedure as specified in the Owner's Manual.
A B
Indoor
side
1
2
3
11

Annual maintenance

Indoor
power
inter-unit
For an air conditioning system that is operated on a regular basis, cleaning and maintenance of the indoor / outdoor
wiring
units are strongly recommended.
As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor / outdoor units will need to be
cleaned at least once every 3 months. This cleaning and maintenance should be carried out by a qualified service
person.
Failure to clean the indoor / outdoor units regularly will result in poor performance, icing, water leaking and even
compressor failure.
34-EN