24-V Wiring; Accessories - Carrier WEATHERMAKER 8000 58ZAV Installation And Operating Instructions Manual

Downflow/horizontal induced-combustion furnaces
Hide thumbs Also See for WEATHERMAKER 8000 58ZAV:
Table of Contents

Advertisement

INSTALLATION
POSITION
OF FILTERS
RETURN-AIR
PLENUM
ACCESS DOOR
Fig. 12—Downflow Filter Arrangement
Table 5—Maximum Capacity of Gas Pipe *
NOMINAL IRON
INTERNAL
PIPE SIZE
DIAMETER
(IN.)
(IN.)
1/2
0.622
3/4
0.824
1
1.049
1-1/4
1.380
1-1/2
1.610
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a
pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table
10-2 NFPA 54/ANSI Z223.1-1999.
VOLTS—
UNIT SIZE
HERTZ—
PHASE
050-08
115—60—1
050-12
115—60—1
070-08
115—60—1
070-12
115—60—1
096-12
115—60—1
096-16
115—60—1
115-16
115—60—1
115-20
115—60—1
115-22
115—60—1
135-20
115—60—1
* Permissible limits of the voltage range at which the unit will operate satisfactorily.
† Time-delay type is recommended.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
AIRFLOW
A88486
LENGTH OF PIPE (FT)
10
20
30
40
175
120
97
82
360
250
200
170 151
680
465
375
320 285
1400
950
770
660 580
2100 1460 1180 990 900
Table 6—Electrical Data
OPERATING VOLTAGE RANGE
Maximum*
Minimum*
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
GAS
SUPPLY
MANUAL
SHUTOFF
VALVE
(REQUIRED)
SEDIMENT
TRAP
UNION
Fig. 13—Typical Gas Pipe Arrangement
The cabinet MUST have an uninterrupted or unbroken ground
according to NEC ANSI/NFPA 70-1999 and Canadian Elec-
trical Code CSA C22.1 or local codes to minimize personal
injury if an electrical fault should occur. This may consist of
electrical wire or conduit approved for electrical ground when
installed in accordance with existing electrical codes. Do not
use gas piping as an electrical ground. Failure to follow this
warning could result in electrical shock, fire, or death.
50
73

24-V WIRING

Make field 24-v connections at the 24-v terminal strip. (See Fig.
14.) Connect terminal Y as shown in Fig. 15 for proper operation
in cooling mode. Use AWG No. 18 color-coded wire only.
The 24-v circuit contains an automotive-type, 3-amp fuse located
on the main control. Any direct shorts during installation, service,
or maintenance could cause this fuse to blow. If fuse replacement
is required, use ONLY a 3-amp fuse of identical size.

ACCESSORIES

1. Electronic Air Cleaner (EAC)
MAXIMUM
MINIMUM
UNIT AMPS
WIRE GAGE
6.6
14
8.1
14
6.7
14
8.4
14
9.2
14
10.2
14
10.1
14
13.3
12
15.2
12
14.3
12
11
MAXIMUM
MAXIMUM WIRE
FUSE OR CKT BKR
LENGTH FT‡
AMPS†
42
15
34
15
42
15
33
15
30
15
28
15
28
15
33
20
29
20
31
20
A89414