F018
Preset Speed #1
Program Pattern Run Preset Speeds
Up to 15 output frequency values that fall within the Lower Limit and the
Upper Limit range may be programmed into the drive and output as a Preset
Speed. This parameter assigns an output frequency to binary number 0001 and
is identified as Preset Speed #1. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed.
Perform the following setup to allow the system to receive Preset Speed
control input at the S1 – S4 terminals:
Program Fundamentals Standard Mode Selection Use Terminal
1.
Board.
Program Terminal Selection Input Terminals S1 (set to Preset
2.
Speed Command 1; LSB of 4-bit count). Repeat for S2 – S4 (MSB of 4-bit
count) as Preset Speed Command 2 – 4, respectively (all Normally
Open).
Note:
The default setting of S4 is EOff, but this terminal may be re-
assigned as the MSB.
Program Frequency Setting Preset Speeds 1 (press Enter twice
3.
and set an output frequency as Preset Speed #1; repeat for Preset Speeds 2
– 15 as required).
Program Frequency Setting Preset Speed Mode Use Speed Modes
4.
(Enable/Disable).
When Enabled, the direction, accel/decel, and torque settings of the
Preset Speed being run are used.
When Disabled, only the speed setting of the Preset Speed being run is
used.
5.
Place the system in the Remote mode (Local|Remote LED Off).
6.
Provide a Run command (connect F and/or R to CC).
Connect S1 to CC to run Preset Speed #1 (S1 to CC = 0001 binary).
With S1 – S4 configured to output Preset Speeds
may be applied to S1 – S4 of the Terminal Board to run the associated Preset
Speed. If bidirectional operation is required, F and R must be connected to CC,
and Use Speed Modes must be enabled at F380.
With S1 being the least significant bit of a binary count, the S1 – S4 settings
will produce the programmed speed settings as indicated in the Preset Speed
Truth Table to the right.
Preset Speeds are also used in the Pattern Run mode.
Preset Speed #2
Program Pattern Run Preset Speeds
This parameter assigns an output frequency to binary number 0010 and is
identified as Preset Speed #2. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
on this parameter).
HX7+ ASD Installation and Operation Manual
(F115
– F118), 0001 – 1111
F018
for further information
Direct Access Number — F018
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed Truth Table.
S4
S4
S1
S1
Preset
Preset
S3
S3
S2
S2
MSB
MSB
LSB
LSB
1
1
0
0
0
0
0
0
2
2
0
0
0
0
1
1
3
3
0
0
0
0
1
1
4
4
0
0
1
1
0
0
5
5
0
0
1
1
0
0
6
6
0
0
1
1
1
1
7
7
0
0
1
1
1
1
8
8
1
1
0
0
0
0
9
9
1
1
0
0
0
0
10
10
1
1
0
0
1
1
11
11
1
1
0
0
1
1
12
12
1
1
1
1
0
0
13
13
1
1
1
1
0
0
14
14
1
1
1
1
1
1
15
15
1
1
1
1
1
1
Note: 1 = Terminal connected to CC.
Note: 1 = Terminal connected to CC.
Direct Access Number — F019
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
F019
Output
Output
1
1
F018
0
0
F019
F019
1
1
F020
F020
0
0
F021
F021
1
1
F022
F022
0
0
F023
F023
1
1
F024
F024
0
0
F287
F287
1
1
F288
F288
0
0
F289
F289
1
1
F290
F290
0
0
F291
F291
1
1
F292
F292
0
0
F293
F293
1
1
F294
F294
79

Advertisement

Table of Contents
loading

Table of Contents