Panel Menu
The Panel menu is accessed by pressing ESC from the
of the Panel menu are effective for keypad control only.
The Panel menu provides quick access to the following menu parameters:
Direction — Forward or Reverse.
Stop Pattern — The Decel Stop or Coast Stop selection determines the method used to stop the
motor when using the Stop|Reset key of the keypad. The Decel Stop setting enables the Dynamic
Braking system setup at
The Coast Stop setting allows the motor to stop at the rate allowed by the inertia of the load.
Note:
V/f Group — One of four V/f profiles may be selected and run. Each V/f profile is comprised of four
user settings: Base Frequency, Base Frequency Voltage, Manual Torque Boost, and Motor
Overload Protection. Expanded descriptions of these parameters may be found in the section titled
Direct Access Parameter Information on pg.
Accel/Decel Group — One of four Accel/Decel profiles may be selected and run. Each of the
Accel/Decel profiles is comprised of three user settings: Acceleration, Deceleration, and Pattern.
Expanded descriptions of these parameters may be found in the section titled
Parameter Information on pg.
Feedback in Panel Mode — This feature enables or disables the PID feedback function.
Torque Limit Group — This parameter is used to select one of four preset positive torque limits to
apply to the active motor (of a multiple motor configuration). The settings of profiles 1 – 4 may be
setup at F441, F444, F446, and F448, respectively.
52
F304
or the DC Injection Braking system setup at F250, F251, and F252.
The Stop Pattern setting has no effect on the Emergency Off settings of F603.
72.
Frequency Command
72.
HX7+ ASD Installation and Operation Manual
screen. The control settings
Direct Access