Burner control unit flow chart
Phase
08
VPS decision: Valve leak test
09
VPS: Empty intermediate valve space
10
VPS test time: Valve 1
11
VPS: Fill intermediate valve space
12
VPS detection: Gas pressure
13
VPS test time: Valve 2
14
Pre-purge time
16
Ignition setting
17
Gas detection: Min. gas pressure switch
18
Pre-ignition time
19
Ignition safety time (SZA)
20
SZA flame detection
21
Flame stabilising time
23
Transition to control mode
24
Control mode
25
Transition after controlled shutdown
32
Burner run-on time
33
Post-purge time
34
Restart blocking time
01
Waiting for heat demand
In the case of fault shutdown:
35
Gas shortage: Min. gas pressure switch
36
On hold program
(cont.)
Burner control unit flow chart
Duration
0.1 s
1 to 3 s
1 to 240 s
1 to 3 s
0.1 s
1 to 240 s
0 to 1 h
max. 2 min
0 ...
0 to 1 min
0.5 to 9.4 s
0.5 s
1 to 200 s
max. 2 min
0 ...
1 to 30 s
1 to 60 s
0 to 1 h
0 to 1 h
0 ...
0 ...
0 ...