Checking The Co2 Content - Viessmann Vitocrossal 300 Service Instructions Manual

Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Commissioning, inspection, maintenance

Checking the CO2 content

Preparing the test
C
D
E
F
Fig. 5
CO
test at the upper heating output
2
C
D
E
F
Fig. 6
B
A
Fig. 7
12
1. Open the gas shut-off valve.
2. Start the burner.
3. Press "S"
and "-"
E
D
Display
then shows the following:
C
Status: "d" (= control stop)
Service: Modulation level in % ("00" = 100 % =
upper heating output, "0" = 0 % = lower heating
output)
1. Press "+"
until the service display has incre-
F
mented to "00" (= 100 %).
2. Note
The CO
content for all natural gases must be
2
between 7.5 and 10.5 %.
Check the CO
content at the flue pipe.
2
Rated heating
Permissible CO
output in kW
%
400
8.6
500
8.6
630
8.6
3. If the CO
content needs adjusting:
2
Remove cap
B
.
Turn setting screw
A
Allen key) until the CO
specified range:
Turning clockwise
CO
content falls
2
Turning anti-clockwise
CO
content rises
2
4. Record the actual value in the report (on page
54).
!
Please note
The CO
content must always be lower in
2
partial load than it is in full load.
simultaneously.
content in
2
0.3
±
0.3
±
0.3
±
in small increments (3 mm
content lies within the
2