Further details regarding the individual steps
qQ Extension kit for one heating circuit
with mixer M2
qW Heating circuit with mixer M3
qE Temperature limiter for limiting the
maximum temperature of underfloor
heating systems
qR Flow temperature sensor M3
Required coding
Multi-boiler system with Vitotronic 300-K
Note
Codes for multi-boiler system, see
Vitotronic 300-K installation and service
instructions
Adjusting the heating curves (only for weather-compensated
control units)
The heating curves illustrate the relation-
ship between the outside temperature
and the boiler water or flow tempera-
ture.
To put it simply: The lower the outside
temperature, the higher the boiler water
or flow temperature.
Commissioning, inspection, maintenance
qT Heating circuit pump M3
qZ Extension kit for one heating circuit
with mixer M3
qU Low loss header
qI Flow temperature sensor, low loss
header
The room temperature, again, depends
on the boiler water or the flow tempera-
ture.
Settings in the delivered condition:
■ Slope = 1.4
■ Level = 0
(cont.)
Address
01:2
31