8.6.2 Node Status

Input form DISP MODE
Execution result (example)
>disp mode
mode
message : enable
cyclic : enable
LNK
ERR
PVERR
GDLINK : ON (10M - Half Duplex)
DPADR
TEST
>
Contents
Status
mode
message
Cyclic
LNK
ERR
PVERR
GDLNK
DPADR
TEST
When FL654 is down mode, the down code is displayed under "mode".
8.6 Gathering RAS information using Hyper Terminal
: RUN(I/O-RUN)
: ON
: OFF
: OFF
: OFF
: OFF
Table 8-3 Node status
The state of the FL654 is displayed.
RUN ... Join in the network, and the I/O operation is executed
STBY ... Join in the network, and the I/O operation is stopped
DOWN ... Down mode
Display of enable / disable for message data transmission
Display of enable / disable for cyclic data transmission
Display of join in (ON) / leave from (OFF) the network
Display of abnormality (ON) / normality (OFF) of the parameter
Display of the protocol version disagreement
Detection (ON) / No detection (OFF)
Display of the result of the transmission line link test
Normality (ON) / Abnormality (OFF)
Display of the detection of duplicated node number
Detected (ON) / Not detected (OFF)
Always turning off
Contents
8